Field Settings from Outdoor Unit
SiUS331708EA
123
Field Settings and Test Operation
2.6
Setting of Low Noise Operation and Demand Operation
Setting of Low Noise Operation
By connecting the external contact input to the low noise input of the external control adaptor for outdoor unit
(optional), you can lower operating noise by 2-3 dB.
When the low noise operation is automatically carried out at night (The external control adaptor for
outdoor unit is not required)
1. While in setting mode 2, select a night-time low noise level for the item 2-22.
2. If necessary, while in setting mode 2, select a starting time of night-time low noise operation for the item 2-26.
(Use the starting time as a guide since it is estimated according to outdoor temperatures.)
3. If necessary, while in setting mode 2, select an ending time of night-time low noise operation for the item 2-27.
(Use the ending time as a guide since it is estimated according to outdoor temperatures.)
4. If necessary, while in setting mode 2, set the item 2-29 (Capacity precedence) to ON.
(If the condition is set to ON, when the air-conditioning load reaches a high level, the system enters to normal
operation mode even during night-time.)
Image of operation
Operation sound
Rated
Level 1
Level 2
Level 3
Time set with night-time low noise start setting
If capacity precedence is set in capacity
precedence setting, the fan speed will be
increased according to the load of air
conditioning when load is heavier.
Night time
Time set with night-time low noise end setting
Operation sound during
night-time low noise mode
can be set with night-time
low noise level setting.
(Factory setting is OFF.)
Operation sound level set with
night-time low noise setting
Set with night-time low noise start setting.
(Factory setting is 10:00 PM.)
Set with night-time low noise end setting.
(Factory setting is 08:00 AM.)
12:00 PM
10:00 PM
08:00 PM
08:00 AM
07:00 AM
06:00 AM
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...