SiAF341904E
Capacity Range
Part 1 General Information
15
4. Capacity Range
4.1 Capacity Range for
VRV
Indoor Units Only
4.1.1 Connection Ratio
Type
Min.
connection
ratio
Max. connection ratio
FXMQ-PB
FXAQ-P
Including
FXFSQ25AR
at least one unit
Other
indoor unit
models
Single outdoor unit
50%
200%
130%
200%
Double outdoor units
160%
Triple outdoor units
130%
Connection ratio =
Total capacity index of the indoor units
Capacity index of the outdoor units