Field Settings for Indoor Unit
SiAF341904E
106
Part 5 Field Settings and Test Operation
1. Field Settings for Indoor Unit
1.1 Field Settings from Remote Controller
Individual function of indoor unit can be changed from the remote controller. At the time of
installation or after service inspection / repair, make the field setting in accordance with the
following description.
Wrong setting may cause error.
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be
required to change. Refer to information in the option handbook.)
1.1.1 BRC1E62, BRC1E63
1
Press and hold
Cancel
button for 4
seconds or more.
Service settings menu is displayed.
2
Select
Field settings
in the service
settings menu, and press
Menu/Enter
button.
Field settings screen is displayed.
3
Highlight the mode, and select desired
mode No. by using (Up/Down)
button.
4
In the case of setting per indoor unit
during group control (When Mode No.
such as
20
,
21
,
22
,
23
,
25
are
selected), highlight the unit No. and
select indoor unit No. to be set by
using (Up/Down) button. (In the
case of group total setting, this
operation is not needed.)
In the case of individual setting per
indoor unit, current settings are
displayed. And, second code No.
“ - ” means no function.
5
Highlight second code No. of the first
code No. to be changed, and select
desired second code No. by using
(Up/Down) button. Multiple identical
mode number settings are available.
In the case of group total setting, all
of second code No. which may be
set are displayed as “
”.
“
” is changed to second code No.
to be set. And, second code No. “ - ”
means no function.
Basic screen
Service settings menu screen
Press
Menu/Enter
button.
Field settings screen
Press
Menu/Enter
button.
First code No.
Second code No.
(1)
(2)
(3)
(4)
(5)
(3)
(5)
In the case of individual
setting per indoor unit
In the case of group total