Outline of Control (Indoor Unit)
Part 4 Functions and Control
103
8.11 Circulation Airflow (FXFSQ only)
Unevenness of room temperature and the startup time are improved by repeating 2-direction
horizontal blow-off and swing alternately.
8.11.1 Initiation Conditions of Circulation Operation
When operation starts (in the startup state)
Circulation airflow operation is performed.
During normal operation
The unit automatically determines operation based on the room temperature condition and time
to switch circulation airflow operation and the normal auto airflow rate and direction (eco full
automatic control).
8.11.2 Operational Concept (Standard Panel)
Cooling
: Factory setting
Circulation airflow operation continues for up to 90 minutes
Set temp.
Target temp.
Δ
t
Circulation airflow
Auto airflow rate and direction
Circulation airflow
Time
Room temp.
Movement pattern
(a)
(b)
(c)
(d)
Appearance
Time (sec.)
13 (23)-14
01: Pattern 1
120
600
120
600
02: Pattern 2
120
600
0
0
03: Pattern 3
0
0
120
600
04: Pattern 4
120
600
120
600
Indicates the horizontal flap is in the position of reducing airflow volume (the flap is inverted).