5 Preparation
Installer reference guide
10
35R5V1B RXM20~35R5V1B
R32 Split Series
4P519439-8H – 2020.07
b
a
b
c
a
Baffle plate
b
Prevailing wind direction
c
Air outlet
Do NOT install the unit in the following places:
▪ Sound sensitive areas (e.g. near a bedroom), so that the
operation noise will cause no trouble.
Note: If the sound is measured under actual installation
conditions, the measured value might be higher than the sound
pressure level mentioned in Sound spectrum in the data book due
to environmental noise and sound reflections.
INFORMATION
The sound pressure level is less than 70 dBA.
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall
off or cause water leakage.
It is NOT recommended to install the unit in the following places
because it may shorten the life of the unit:
▪ Where the voltage fluctuates a lot
▪ In vehicles or vessels
▪ Where acidic or alkaline vapour is present
Seaside installation.
Make sure the outdoor unit is NOT directly
exposed to sea winds. This is to prevent corrosion caused by high
levels of salt in the air, which might shorten the life of the unit.
Install the outdoor unit away from direct sea winds.
Example:
Behind the building.
b
c
a
If the outdoor unit is exposed to direct sea winds, install a
windbreaker.
▪ Height of windbreaker≥1.5×height of outdoor unit
▪ Mind the service space requirements when installing the
windbreaker.
a
b
c
d
c
d
a
Sea wind
b
Building
c
Outdoor unit
d
Windbreaker
The outdoor unit is designed for outdoor installation only, and for
ambient temperatures ranging from –10~50°C in cooling mode and
from –20~24°C in heating mode.
5.2.2
Additional installation site requirements
of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.
a
b
c
c
d
a
Snow cover or shed
b
Pedestal
c
Prevailing wind direction
d
Air outlet
In any case, provide at least 300 mm of free space below the unit.
Additionally, make sure the unit is positioned at least 100 mm above
the maximum expected level of snow. See
In heavy snowfall areas it is very important to select an installation
site where the snow will NOT affect the unit. If lateral snowfall is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.
5.2.3
Refrigerant piping length and height
difference
What?
Distance
Maximum allowable pipe length
20 m
Minimum allowable pipe length
1.5 m
Maximum allowable height difference
15 m