Troubleshooting
Service Diagnosis
88
4.23 Electrical Box Temperature Rise
Error Code
L3
Method of Error
Detection
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
compressor off.
Error Decision
Conditions
With the compressor off, the radiation fin temperature is above
A
°C.
The error is cleared when the radiation fin temperature drops below
B
°C.
To cool the electrical components, the outdoor fan starts when the radiation fin temperature
rises above
C
°C and stops when it drops below
B
°C.
Supposed
Causes
Defective outdoor fan motor
Short circuit
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Troubleshooting
Check No.17
Refer to P.98
Check No.19
Refer to P.99
A
(°C)
B
(°C)
C
(°C)
20/25/35 class
98
75
83
50 class
122
64
113
Caution
WARNING
To cool the electrical components,
the outdoor fan starts when the
radiation fin temperature rises
above
C
°
C and stops when it
drops below
B
°
C.
(R19556)
YES
NO
YES
NG
NO
OK
NO
YES
Turn off the power and turn it on
again.
Check the radiation fin
temperature.
Radiation fin dirty?
Check No. 19
Check the outdoor fan.
Error again or outdoor
fan activated?
Replace the outdoor unit
PCB.
Clean up the radiation fin.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the outdoor fan
motor.
Correct the connectors
and fan motor lead wire.
Replace the outdoor unit
PCB.
Above
A
˚C?
Check the installation
condition.
Go to
Check No. 17
.
Summary of Contents for RXG20L2V1B
Page 12: ...SiBE041401E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Page 14: ...SiBE041401E 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Page 60: ...SiBE041401E 49 Remote Controller Part 5 Remote Controller 1 Remote controller 50 ...
Page 113: ...SiBE041401E Check Service Diagnosis 102 50 class Diode bridge R19944 ...
Page 127: ...Revision History Month Year Version Revised contents 03 2014 SiBE041401E First edition ...