Field Settings
SiBE041401E
109
Trial Operation and Field Settings
3.4
Jumper Settings
Indoor Unit
For the location of the jumper, refer to page 9.
Outdoor Unit
For the location of the jumper, refer to page
.
Caution
Replace the PCB if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of
them.
Function
Jumper
When connected
(factory setting)
When cut
Fan speed setting when
compressor stops for
thermostat OFF. (effective only
in cooling operation)
JB
The fan stops.
Fan speed setting ;
Remote controller setting
Power failure recovery function
JC
Auto-restart
The unit does not resume
operation after recovering from a
power failure. Timer settings are
cleared.
Function
Jumper
When connected
(factory setting)
When cut
Improvement of
defrost performance
20/25/35 class
→
J5
50 class
→
J8
Standard control
Reinforced control (Ex: The
frequency increases, the
duration time of defrost
lengthens.)