4 Installation

Installation manual

9

RXA20~35A2V1B
R32 split series
3P517827-1 – 2017.12

4.5

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on  the  site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

DANGER: RISK OF ELECTROCUTION

Disconnect  the  power  supply  for  more  than  10  minutes,
and  measure  the  voltage  at  the  terminals  of  main  circuit
capacitors  or  electrical  components  before  servicing.  The
voltage MUST be less than 50 V DC before you can touch
electrical  components.  For  the  location  of  the  terminals,
see the wiring diagram.

DANGER: RISK OF ELECTROCUTION

All  electrical  parts  (including  thermistors)  are  powered  by
the power supply. Do not touch them with bare hands.

DC-

DC+

g

h

b c d e

f

a

a

Multimeter (DC voltage range)

b

S70 – fan motor lead wire

c

LED

d

S90 – thermistor lead wire

e

S20 – electronic expansion valve lead wire

f

S80 – reversing solenoid valve lead wire

g

S40 – thermal overload relay lead wire

h

DB1 - diode bridge

4.5.1

Guidelines when connecting the electrical
wiring

Tightening torques

Item

Tightening torque (N•m)

M4 (X1M)

1.5~1.6

M4 (earth)

1.4~1.5

4.5.2

Specifications of standard wiring
components

Component

RXA

20

25+35

Power supply
cable

Voltage

220~240 V

Phase

1~

Frequency

50 Hz

Wire sizes

MUST comply with applicable

legislation

Interconnection cable
(indoor↔outdoor)

4-core cable ≥1.5 mm² and applicable

for 220~240 V

Recommended field fuse

10 A

13A

Earth leakage circuit
breaker

MUST comply with applicable

legislation

4.5.3

To connect the electrical wiring on the
outdoor unit

1

Open the wire clamp.

2

Connect the interconnection cable and power supply as follows:

50Hz

220-240V

c

d

f

a

e

b

a

Interconnection cable

b

Power supply cable

c

Field fuse

d

Earth leakage circuit breaker

e

Power supply

f

Earth

3

Tighten  the  terminal  screws  securely.  We  recommend  using  a
Phillips screwdriver.

4.6

Finishing the outdoor unit
installation

4.6.1

To finish the outdoor unit installation

DANGER: RISK OF ELECTROCUTION

▪ Make sure that the system is earthed properly.

▪ Turn off the power supply before servicing.

▪ Install  the  service  cover  before  turning  on  the  power

supply.

1

Insulate and fix the refrigerant piping and interconnection cable
as follows:

f

b

a

e

d

c

Summary of Contents for RXA20A2V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXA20A2V1B RXA25A2V1B RXA35A2V1B...

Page 2: ...s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standa...

Page 3: ...klist before commissioning 10 5 2 Checklist during commissioning 10 5 3 To perform a test run 10 6 Configuration 10 6 1 To set the facility mode 10 7 Troubleshooting 11 7 1 Fault diagnosis using LED o...

Page 4: ...he air inlet facing the wall and NOT directly exposed to the wind b a b c a Baffle plate b Prevailing wind direction c Air outlet Do NOT install the unit in sound sensitive areas e g near a bedroom so...

Page 5: ...fference 15 m 3 2 3 Refrigerant piping insulation Pipe outer diameter p Insulation inner diameter i Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 9 5 mm 3 8 12 15 mm i i t p p If the temperature is...

Page 6: ...outdoor unit from falling over In case the unit is installed in places where strong wind can tilt the unit take following measure 1 Prepare 2 cables as indicated in the following illustration field su...

Page 7: ...with nitrogen gas up to a gauge pressure of at least 200 kPa 2 bar It is recommended to pressurize to 3000 kPa 30 bar in order to detect small leaks 2 Check for leaks by applying the bubble test solut...

Page 8: ...4 4 3 To determine the additional refrigerant amount If the total liquid piping length is Then 10 m Do NOT add additional refrigerant If the total liquid piping length is Then 10 m R total length m o...

Page 9: ...ELECTROCUTION All electrical parts including thermistors are powered by the power supply Do not touch them with bare hands DC DC g h b c d e f a a Multimeter DC voltage range b S70 fan motor lead wire...

Page 10: ...etween the outdoor unit and the indoor unit Drainage Make sure drainage flows smoothly Possible consequence Condensate water might drip The indoor unit receives the signals of the user interface The s...

Page 11: ...r before removing the refrigerant piping If the compressor is still running and the stop valve is open during pump down air will be sucked into the system Compressor breakdown or damage to the system...

Page 12: ...N E HA HE HL HN HR MR _A MR _B S U V W X A K R_ CONNECTION CONNECTOR Q L OVERLOAD PROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER RC RECEIVER F...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...3P517827 1 2017 12 Copyright 2017 Daikin...

Reviews: