DAIKIN ROOM AIR CONDITIONER

INSTALLATION MANUAL

R410A Split Series

Installation manual

Manuel dinstallation

Manual de instalación

Manuel dinstallation

00_CV_3P686858-1.indd   1

2022/02/14   17:04:09

Summary of Contents for RX15WMVJU9

Page 1: ...MVJU9 RX36WMVJU9 RK30WMVJU9 RK36WMVJU9 RXL15WMVJU9 RXL18WMVJU9 RXL24WMVJU9 DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instala...

Page 2: ...g can cause a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes could cause a gas leak and potential explosion causing severe injury or death If refrigerant g...

Page 3: ...or moisture should be prevented from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultra...

Page 4: ...ater will flow from the drain of the outdoor unit do not place anything under the unit which must be kept away from moisture 9 A location where flammable gas does not leak Position at least 6 5 8ft 2m...

Page 5: ...hortest pipe length is 10ft 3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which...

Page 6: ...ed to either change the orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately Outdoor Unit Installation 1 Installing the outdoor unit When installing t...

Page 7: ...mperial type Conventional are tool Cut exactly at right angles Remove burrs 4 Refrigerant piping CAUTION Use the flare nut fixed to the main unit This is to prevent the flare nut from cracking as a re...

Page 8: ...16 inch 40mm or more 0 031 inch 0 8mm C1220T O I D 9 16 5 8 inch 14 16mm Use separate thermal insulation pipes for gas and liquid refrigerant pipes Using finishing tape bundle and wrap the indoor uni...

Page 9: ...id stop valve turn the rod of the valve 90 counter clockwise using a hexagonal wrench Close it after 5 seconds and check for gas leakage Using soapy water check for gas leakage from the indoor unit s...

Page 10: ...ower supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place Round crimp style terminal Stranded wire Screw Flat washer Screw Screw Flat was...

Page 11: ...supply terminal block Shape wires so that the service lid ts securely Service lid Screws L1 L2 Conduit Lock nut Conduit mounting plate RX30 36 RK30 36 RXL18 24 models Shape wires so that the service...

Page 12: ...1 Remove the top plate of the outdoor unit 6 screws 2 Remove the front plate 8 screws 3 Remove the anti drip cover 4 Cut the jumper J6 of the PCB inside Front plate Anti drip cover Top plate Cut jump...

Page 13: ...he drain pan heater in accordance with the installation manual included with the drain pan heater 2 Cut the jumper J9 of the PCB inside Cut jumper J9 J9 J4 J6 RX30 36 RK30 36 RXL18 24 models 1 Attach...

Page 14: ...ote controller 2 Press and hold the Cancel button for 4 seconds or longer Service settings menu is displayed 3 Select Test Operation in the service settings menu and press the Menu OK button Basic scr...

Page 15: ...to the installation manual for the indoor unit 2 Test items Test items Symptom Check Indoor and outdoor units are installed securely Fall vibration noise No refrigerant gas leaks Incomplete cooling h...

Page 16: ...Two dimensional bar code is a manufacturing code 3P686858 1 M21B536 2205 HT 00_CV_3P686858 1 indd 2 2022 02 14 17 04 09...