SiUS092230EA
Troubleshooting for FDMQ, FFQ Series
Part 6 Service Diagnosis
149
Note
6.7 Presence Sensor or Floor Sensor Abnormality
Applicable
Models
FFQ09/12/15/18W2VJU9(8)
Error Code
CE
Method of Error
Detection
The system detects abnormality by the output signal from the sensor(s).
Error Decision
Conditions
The sensor is disconnected or shorted while the unit is running.
Supposed
Causes
Disconnection of connector
Breaking of wires
Defective sensor(s)
Defective sensor kit PCB
Troubleshooting
If the cause of the problem is related to the sensors, the sensors should be checked prior to
changing the indoor unit PCB.
When replacing the defective sensor(s), replace the sensor kit as ASSY.
(R24577)
YES
NO
Check the connection of
connectors on the sensor kit.
YES
NO
Caution
Correct the connection.
Connect the connectors
properly.
Normal?
Normal?
Turn off the power. Then, turn on
the power to restart the system.
YES
NO
Normal
Replace the sensor kit.
CE
error
displayed again?
Check the connection of
connector X81A on indoor unit
PCB.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for RX-W Series
Page 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Page 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Page 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...