Standard Control: Resistance 

In Resistance Control Mode the RTD-
10 Inputs allow individual control of 
a/c unit operating parameters using 
resistance values. Each input 
corresponds to a specific unit setting 
shown in the table below If an input is 
left unconnected then the 
corresponding setting will remain at 
the default value.

S1

Setpoint

0..10kΏ : 16..32°C (

22

)

S2

Fanspeed

Low<=1.1kΏ, 

High

=2.2kΏ, HighHigh*=3.3kΏ

S3

Mode

Auto

<=1.1kΏ, Heat=2.2kΏ, Fan=3.3kΏ, Cool=4.7kΏ, Dry=6.8kΏ,

S4

Louvre

Swing<=1.1kΏ, 

=2.2kΏ, 20°=3.3kΏ, 70°=4.7kΏ, 90°=6.8kΏ,

S5

On/off

On = Closed Circuit, 

Off

 = Open Circuit

S6

Unlock

Lock All<=1.1kΏ, Lock Setpoint, Mode, On/Off= 2.2kΏ, Lock 
Mode,On/Off=3.3kΏ, Lock On/Off=4.7Ώ, Local=6.8kΏ, Lock 
Mode=9.6kΏ, 

Unlock

>15kΏ

*HighHigh fanspeed operates if available, otherwise selects High fanspeed

S1 kΏ

0.3 0.9

1.5

2.1

2.6

3.2

3.8

4.4

5.0

5.6

6.2

6.8

7.4

7.9

8.5

9.1

9.7

R1

Run/
Defrost

Run: SW1.3 OFF : Closed when unit switched ON 
Defrost: SW1.3 ON : Closed when unit in defrost

R2

Fault

Closed on any unit fault

Caution

: Relays rated for maximum 1A, 24VAC/30VDC

Resistances should be /-250 ohms of the quoted value. Open circuit is R>200k

.

S1 in resistance mode is designed to be operated using a 

linear

 10k

 variable resistance.

It is recommended that volt-free contacts or switch mechanisms have gold plated contacts to ensure a low 
resistance circuit when the switch is made.

S1 to S6 cables should be 0.5 to 1.0 mm

2

 multi-stranded screened twisted pair. The screen should be earthed 

at one end only. The maximum distance from the RTD-10 to the input source is 200m.

Mounting

88.00

78.00

Ø 5.00

MOUNTING PILLARS

The RTD-10 is supplied with 4 
mounting pillars that can be used to 
mount the interface within units with 
compatible mounting holes

SCREW MOUNTING

The RTD-10 can be mounted using 
screws of up to 5mm diameter. 

The RTD-10 can be mounted horizontally or vertically.

Power Supply

The RTD-10 requires a 15V to 24VDC power connection. Power can be 
supplied from VRV indoor unit PCB X18A connection , a Skyair indoor unit 
PCB X35A connection or VAM PCB X11A connection. A 1m cable and 
connector is supplied with the RTD-10.

RTD-10 Description

The RTD-10 is a monitoring and control interface for Daikin VRV and Skyair 
ranges of air-conditioners; and VAM and VKM ventilation units. The interface is 
compatible with all units that have a P1,P2 remote controller network 
connection and allows control of up to 16 units in a single group. 

Control Functions

HARDWIRED CONTROL.  Unit control can be achieved through resistance 
inputs using resistor, potentiometer and volt-free contact inputs.

BMS INTEGRATION.  Unit control can be achieved through 1-10V voltage 
inputs integrated with BMS control outputs.

HEATING INTERLOCK. Units can be interlocked with external heating 
systems.

DUTY/STANDBY. Multiple groups can be operated with rotating duty/standby 
with fault and high temperature alarming.

MODBUS CONTROL. The RTD supports the Modbus Protocol for network 
control and monitoring.

CUSTOM CONTROL. RTD interfaces can be supplied in custom configurations 
to suit specific applications.

                                                                                                         

Warnings and Cautions

Do not exceed the specified fault relay ratings

Observe precautions for handling Electrostatic 
Sensitive Devices

RTD-10 Control Interface v1.04

Installation and Operating Instructions

P1,P2 Network

Terminals P1, P2 connect to the Daikin P1, P2 network. P1,P2 installation 
should follow Daikin installation specifications. The RTD-10 can operate in 
Master or Slave mode with any Daikin remote controller. Operation is also 
possible without a remote controller being connected. Note that infra-red 
receivers must be configured to operate in slave mode.

The RTD-10 can be configured to operate in several different modes using the 
configuration DIP switches SW1.1 to SW1.4. In Standard Control the following 
combinations of modes are available:

Input 
Mode

5 6 7 8

ON

1 2 3 4

Resistance

5 6 7 8

ON

1 2 3 4

 

Voltage

Relay R1 
Output

5 6 7 8

ON

1 2 3 4

 

Unit Run

Unit Run

5 6 7 8

ON

1 2 3 4

 

Defrost 
Operation

Setpoint 
Limit

5 6 7 8

ON

1 2 3 4

No Limit

5 6 7 8

ON

1 2 3 4

 

Limit 19 to 23 

S1

S2

S3

S4

S5

S6

0V

0V

S1

S2

S3

RESISTANCE MODE

S4

S5

S6

5 6 7 8

ON

1 2 3 4

 Standard Control

Indoor Unit

Remote

Controller

(master)

P1

P2

P1

P2

P1

P2

P1

P2

upto 16 units

Indoor Unit

RTD

0V

+V

POWER

15-24VDC

0V

+V

X18A

VRV

Indoor

PCB

RED

BLUE

0V

+V

POWER

15-24VDC

0V

+V

X35A

Skyair
Indoor

PCB

RED

BLUE

100.00

100.00

22.00

1

J2

LED5

LED6

LED4

LED3

LED1

LED2

SW1

All dimensions in mm

5 6 7 8

ON

1 2 3 4

S4

S5

S6

0V

S1

S2

S3

0V

RS485 D-BUS

GND

R2

0

+

R1

0

+

0V

+V

POWER

15-24VDC

DB

+

DA

-

REMCON

P1

P2

Daikin Control Interface

RTD-10

Summary of Contents for RTD-10

Page 1: ...ikin VRV and Skyair ranges of air conditioners and VAM and VKM ventilation units The interface is compatible with all units that have a P1 P2 remote controller network connection and allows control of up to 16 units in a single group Control Functions HARDWIRED CONTROL Unit control can be achieved through resistance inputs using resistor potentiometer and volt free contact inputs BMS INTEGRATION U...

Page 2: ...terlock Master Cooling System Inhibit 5 6 7 8 ON 1 2 3 4 R1 Mode Interlock Relay Closed Unit ON No Fault Mode Auto Heat or Heat INTERLOCK SLAVE MODE To operate in slave mode the input S4 operates as a Volt free inhibit input When the inhibit signal is closed circuit the RTD 10 will prevent the A C unit from operating Input S4 operation can be inverted by inserting a Short Circuit on input S2 The R...

Page 3: ...larm occurs due to a unit or communications fault then all units will run until all faults are cleared If a Level 1 or Level 2 alarm occurs due to a high temperature on an indoor unit or the Auxiliary Space sensor then all units will run until temperature has reset and will continue to run on for 20 minutes before reverting to normal Run Standby operation In Test Mode rotation 60s the run on time ...

Page 4: ... written to the A C on every register write On Change updates are only sent if the value written changes Central locks the corresponding RC button Local unlocks the RC button and prevents any updates from the RTD MONITORING Unit data is available for each of the indoor units on the P1 P2 network All readback data is available in analogue Input Registers Input registers are numbered using the indoo...

Reviews: