Operating instructions
24
Daikin RoCon HP
Daikin Control
008.1420844 – 05/2014
3
x
Operation
An active legionella protection function (parameter [Anti-Le-
gionella day]) involves heating the connected storage tank to a
disinfection temperature 1 x a day or 1 x a week. The legionella
protection function is active for an hour.
The maximum hot water temperature set by the user or
the heating technician is ignored when hot water is
heated for disinfection purposes.
A connected circulation pump is automatically switched
on during thermal disinfection.
Setting the parameters for legionella protection is carried out in
the rotary switch setting
"Configuration"
in level
"DHW Con-
figuration"
.
Using the factory settings, the storage tank is heated at 03:30
hours if the target hot water temperature is below 65 °C at that
time.
More detailed explanations and possible setting values for this function can be seen
in chapter 5.2.4.
3.6.12 Reset to factory settings (Reset)
If the Daikin Altherma EHS(X/H) no longer works properly and
any other cause for the malfunction cannot be detected, it may be
helpful to reset all the controller settings to the factory settings.
There are 3 options for this.
Option 1
User access rights
allow the
switching time program
in the
"Special Level" to be reset to the factory setting according to
tab. 3-9.
1. Press the exit button for at least 5 s.
Menu
"Special Level"
is displayed.
2. Select the programme
"Timeprog Reset"
with the rotary
switch.
3. Execute the programme by briefly pressing on the rotary
switch.
The respective values are reset to the factory setting.
4. Select
"Return"
with the rotary switch.
5. Confirm the changes with a brief push of the rotary switch.
Possibility 2
Technician access rights
permit all
customer-specific pa-
rameter settings
in the "Special Level" to be reset to the factory
setting according to tab. 5-1 to tab. 5-11.
1. Enter the expert code (see section 3.6.1).
The
"Setup"
level is displayed after entering.
2. Press the exit button for at least 5 s.
Menu
"Special Level"
is displayed.
3. Select the programme
"Reset?"
with the rotary switch.
4. Execute the programme by briefly pressing on the rotary
switch.
The respective values are reset to the factory setting.
5. Select
"Return"
with the rotary switch.
6. Confirm the changes with a brief push of the rotary switch.
Possibility 3
If fundamental changes to the Daikin Altherma EHS(X/H)
equipment for the function within the RoCon system are nec-
essary, the
Basic Configuration
can be reset using
Technician
access rights
to the
factory settings
or can be redefined.
1. Enter the expert code (see section 3.6.1).
The
"Setup"
level is displayed after entering.
2. Select the
"System Config"
level with the rotary switch.
3. Confirm the changes with a brief push of the rotary switch.
An overview is displayed.
4. Select the programme
"Delete"
with the rotary switch.
5. Confirm the changes with a brief push of the rotary switch.
Restart of the Daikin Altherma EHS(X/H) is performed.
The message "No Basic Configuration" is displayed.
6. Place the rotary switch in the
"Info"
position.
The message "Basic Configuration Not Set" is displayed.
7. There is now the facility either to select manual mode for the
equipment individually (a) or to load the factory settings
automatically (b).
a) Press the rotary switch briefly.
A parameter overview is displayed at the level
"Basic
Configuration"
and the settings can performed manually
as desired according to tab. 5-14.
b) Turn the Daikin Altherma EHS(X/H) off and restart it.
After the has restarted the question will be Daikin
Altherma EHS(X/H) posed whether the standard configu-
ration should be used. If it is confirmed with
"Yes"
, the
preset
basic configuration is loaded
. If the answer
given is
"No"
the settings must be performed manually,
see a)
.
More detailed explanations and possible setting values for this function can be seen
in chapter 5.12.
After a reset to the factory settings via option 2 or 3, the
system must be configured again by the heating tech-
nician to the installation environment and all the cus-
tomer-specific parameters reset.