Operation
Daikin RoCon HP
Daikin Control
008.1420844 – 05/2014
Operating instructions
11
3.4.2 Setting the operating mode
The selection of the operating mode with which the Daikin
Altherma EHS(X/H) is to operate is undertaken on the rotary
switch in the setting
"Operating Mode"
.
The selected operating mode is activated by briefly pushing the
rotary switch.
Operating Mode
Standby
Reducing
Operating Mode
Heating
Cooling
Summer
Operating Mode
Summer
Automatic 1
Automatic 2
Operating Mode
Summer
Automatic 1
Automatic 2
Fig. 3-7
Changing over the operating mode
(E.g.: From "Standby" to "Automatic 1")
●
Place the rotary switch in the
"Operating Mode"
position.
An overview is displayed.
●
Select the desired operating mode with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
Daikin Altherma EHS(X/H) operates in accordance with
the set operating mode.
The current operating mode is indicated by an appropriate
symbol in the standard display.
Operating mode Standby (Stand-by)
CAUTION!
A heating system that is not frost-protected can freeze
in cold weather and be damaged.
●
Drain the water out of the heating system if there is
a danger of frost.
●
If the heating system is not drained and there is a
risk of frost, the power supplies must be secured
and the external main switch must remain switched
on.
In this mode, the Daikin Altherma EHS(X/H) is shifted to the
stand-by mode. The
frost-protection function
(see section 3.6.5) remains in place. In order to maintain this
function, the system must not be disconnected from the mains!
All controllers integrated into the RoCon-system via the CAN bus
are also switched at a higher level to the operating mode
"Standby".
Fig. 3-8
Standard display in "Standby" operating mode
(above the frost-protection limit)
In the "Standby" operating mode, the heat pump and
any optionally connected backup heaters are isolated
from the power supply (
Energy saving mode
) when
the following conditions are met:
– the outdoor temperature sensor (RoCon OT1) is
connected and correctly parametrised in the system
configuration,
– the outdoor temperature is over 8 °C,
– there is no heating command,
– the frost protection function is not active in any of
the connected heating circuits, and
– Daikin Altherma EHS(X/H) has been switched on
for at least 5 mins.
Operating mode Reducing
Reduced heating mode (lower set room temperature) in ac-
cordance with the target temperature set for economy mode in
the parameter [T-Reduced] (see section 3.4.4).
Hot water generation according to the set target domestic hot
water temperatures and switching cycles in the hot water time
programme [DHW Program 1] (see section 3.4.5).
Operating modes Heating, Cooling
Heating or cooling operation in accordance with the room tem-
perature set in the parameter [T-Room 1 Setpoint]
(see section 3.4.3).
A connected outdoor temperature sensor (weather-controlled
flow temperature regulation) or a connected room station will also
influence the set flow temperature regulation (requirements: Pa-
rameter [HC Function] = On).
Hot water generation according to the set target domestic hot
water temperatures and switching cycles in the hot water time
programme [DHW Program 1] (see section 3.4.5).
Operating mode Summer
Hot water generation according to the set target domestic hot
water temperatures and switching cycles in the hot water time
programme [DHW Program 1] (see section 3.4.5).
All controllers integrated into the RoCon-system via the CAN bus
are also switched at a higher level to the operating mode
"Summer".
Operating mode Automatic 1 (Timer programme)
Automatic heating and economy mode in accordance with the
permanent timer programmes (see section 3.4.7):
– [HC Program 1]
– [DHW Program 1]