Parameter settings
Operating Instructions
45
Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
7.8
Error
[→ Main menu → Error]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Emergency
Emergency heating by backup heater or another external heat generator.
-
E
E
Yes
In the event of an error, emergency operation is automatically activated.
No
In the event of an error, emergency operation by manual activation only.
Manual opera-
tion status
Inactive
Activation of the fixed feed temperature control (for diagnostic purposes).
-
E
E
Active
Temperature,
manual opera-
tion
20 – 80 °C
Required feed temperature for manual operation.
50 °C
-
E
E
Tab. 7-22
Parameter in the "Error" menu
7.9
Terminal
[→ Main menu → Terminal]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Terminal ad-
dress
Off
Setting of the terminal ID of the control panel for system access. The set
value must be unique throughout the entire system. Confirmation of this
parameter with the rotary button effects a new initialisation of the controller.
All settings except "Off" authorise the user of the control panel to activate
the terminal function and thus to operate all RoCon system components
with a valid device ID.
Off
1
N
E
0 – 9
Bus scan
Off
No function
Off
-
E
E
On
Controller checks which RoCon devices are connected in the system via
CAN bus lines. Detected devices are displayed in the menu [→ Main menu
→ Terminal] with type and data bus ID (e.g. MM#8 = mixer module with
bus ID 8).
Controller
BM1/BE1 #X
With a detected device only: Activation switches to the heat generator with
the bus ID X (see
, [Bus ID heat generator] parameter).
-
Mixer #X
With a detected device only: Activation switches to the mixer module with
the bus ID X (see
, [Heating circuit assignment] parameter).
-
E
E
Tab. 7-23
Parameter in the "Terminal" menu
7.10
Statistics
[→ Main menu → Statistics]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Energy HP,
cooling
-
The amount of heat delivered by the heat pump for cooling operation is dis-
played in kWh (per month).
-
kWh
S
S
Energy HP,
heating
-
The amount of heat delivered by the heat pump for heating operation is
displayed in kWh (per month).
-
kWh
S
S
Energy, hot
water
-
The amount of heat delivered by the heat pump for domestic hot water pre-
paration is displayed in kWh (per month).
-
kWh
Energy HP
total
-
The total amount of heat delivered by the heat pump is displayed in kWh
(per month).
Electr. energy
total
-
The total electrical power consumed is displayed in kWh (per month).
Ext. energy
source, hot
water
-
The volume of heat of the additional heat generator for domestic hot water
preparation in kWh is displayed.
-
kWh
S
S
Summary of Contents for RoCon+ HP Series
Page 116: ...Betriebsanleitung 116 Daikin RoCon HP Daikin Regelung RoCon HP1 008 1447899_00 09 2019 DE ...
Page 236: ...Gebruiksaanwijzing 236 Daikin RoCon HP Daikin regeling RoCon HP1 008 1447899_00 09 2019 NL ...
Page 351: ...Driftsvejledning 351 Daikin RoCon HP Daikin regulering RoCon HP1 008 1447899_00 09 2019 DA ...
Page 406: ...Instruktionsbok 406 Daikin RoCon HP Daikin reglerenhet RoCon HP1 008 1447899_00 09 2019 SV ...
Page 460: ...Brukerveiledning 460 Daikin RoCon HP Daikin Regulering RoCon HP1 008 1447899_00 09 2019 NO ...
Page 516: ...008 1447899_00 09 2019 EN DE FR NL IT DA SV NO FI Copyright Daikin ...