Si39-406
Precautions for New Refrigerant (R410A)
Precautions for New Refrigerant (R410)
221
4. Leak tester
Specifications
2
Hydrogen detecting type, etc.
2
Applicable refrigerants
R410A, R407C, R404A, R507A, R134a, etc.
Differences
2
Previous testers detected chlorine. Since HFCs do not contain chlorine, new tester detects
hydrogen.
5. Refrigerant oil (Air compal)
Specifications
2
Contains synthetic oil, therefore it can be used for piping work of every refrigerant cycle.
2
Offers high rust resistance and stability over long period of time.
Differences
2
Can be used for R410A and R22 units.
6. Gauge manifold for R410A
Specifications
2
High pressure gauge
- 0.1 to 5.3 MPa (-29.92 inHg to 738 psi)
2
Low pressure gauge
- 0.1 to 3.8 MPa (-29.92 inHg to 530 psi)
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...