Electric Wiring Work
Si39-406
186
Installation Manual BS Unit
7.4
Specifications for Field Supplied Fuses and Wire
NOTE:
1. Select the particular size of electric wire for power line in accordance with the standards of the
given nation and region.
2. Insulated thickness:1/16’’ or more
3. Allowable length of the transmission wiring should be as follows.
Between outdoor unit, BS unit and indoor unit: Max. 3280ft (Total wiring length: 6560ft)
Between BS unit and remote controller: Max. 1640ft
Max. branches No. of branches: 16
4. Up to 16 branches are possible for unit-to-unit cabling. No branching is allowed after branching.
7.5
Gist of Field Line Connection
Remove the side cover of the electric parts box shown in the below figure and connect each
wire.
NOTE:
Keep transmission wiring a minimum of 2’’ from other electric wires so as to avoid the effects of
external noise. (Bundle transmission wiring separate of other wires, with the included tie-wrap.)
Do not connect power wiring to the transmission wiring terminal.
Doing so could damage the entire system.
Model
Power supply wiring
Transmission wiring
Field fuse
Size
Wire
Size
BSVQ36M
15A
Size must comply
with local codes.
Sheathed wire
(2 wire) (NOTE 2)
AWG18-16
BSVQ60M
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
branch
Sub-
branching
A 1 P
F1
F1
F2
F2
L1
L2
Wire
Wire
fitting
Clamp
(Attached)
Clamp
(Attached)
Grounding terminal
Grounding wire
Branch wiring
(To indoor unit)
Power
supply
wiring
Attach insulation
sleeves
Clamp
(Attached)
Branch wiring
(To outdoor unit)
IN/D
OUT/D.BS
Conduit
Lock nut
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...