Si39-406
Refrigerant Piping
Installation Manual REYQ96MTJU
149
Precautions when selecting branch piping.
If the piping between the outdoor unit and the first refrigerant branching kit is 295ft. or longer, be
sure to enlarge the main pipe in the liquid-side piping.
Do not enlarge the main pipe in the discharge-side and suctionside piping.
Depending on the length of the refrigerant piping, the power may drop, but even in such cases it
is ok to enlarge the main pipe.
[Liquid side]
REYQ96MTJU type: .....................
φ
3/8"
→
φ
1/2"
1
2
4
5
6
3
1. Outdoor unit
2. Main pipe
3. Enlarge
4. The first refrigerant branching kit.
5. Indoor unit
6. BS unit
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...