Si39-406
Appendix
General Information
127
7.10.5 Example 5:
Excessive noise due to incorrect angling of REFNET joints
Situation
The noise of the refrigerant flow during defrosting is excessive.
Source of
Problem and
Remedial Action
The angle of the fittings was incorrect and needed to be rectified as shown in the following figure.
1.
REFNET joints
The REFNET joints should be installed such that branches meet the main pipe either
horizontally or vertically at an angle of exactly 90 degrees.
2.
REFNET header
The REFNET header is a lateral flow pipe and should be fitted so as to allow horizontal branch
fittings. (Vertical or sloping fitting is not permissible.)
Main Points
Reasons for using refrigerant branch kit
Fittings of REFNET joints or headers which are not carried out in strict accordance with the
principles outlined here may result in complaints relating, for example, to “poor performance” of
the system or “noisy refrigerant flow”. (To prevent unbalance flow or oil shortage)
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...