7.10 Bad Examples and Good Examples in Installation
7.10.1 Example 1:
Signal interference due to use of multiple core cable
(all
model)
Situation
Although for the purposes of group control there are only 2 units per group there are transmission
malfunctions between the indoor units and the remote controller and the remote controller’s
address display is showing non-existent addresses such as 13 or 15.
Source of
Problem and
Remedial Action
Multiple core cable has been used
for at least part of the interconnecting wiring between the
remote controller and the indoor units.
This has resulted in signal interference leading to a transmission malfunction.
The multiple core cable was replaced by twin core cable and the fault disappeared.
Main Points
Although twin core cable had been run from each unit, multiple core cable was used on the way.
In schools, etc., because remote controllers are often installed in a single first floor control room,
it is easier to use a multi-core cable.
Signal interference can result in non-existent addresses appearing on the display.
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...