SiUS371901EB
Outline of Control (Indoor Unit)
Part 4 Functions and Control
184
Note(s)
9.15 Fan Control (Heater Residual) (FXTQ-TA Models)
Outline
If the indoor heater turned OFF from ON during heating operation, the fan will keep operating for
further period of time in order to cool the heater.
Detail
9.16 Interlocked with External Equipment (FXTQ-TA and
CXTQ-TA Models)
9.16.1 Air Purifier (UV Lamp)
When an air purifier is connected onsite, the fan is operated with the airflow rate set of the remote
controller or with the H tap.
9.16.2 Humidifier
When a humidifier is connected onsite, the fan operates with the airflow rate set of the remote
controller or with the H tap.
This control is not applicable to the humidifier connected to the wiring adaptor, but to the humidifier
connected to HUMIDIFIER on the X1M terminal of the indoor unit PCB.
•
Heater turned OFF from ON
OR
•
Heater ON
•
Time up (
∗
2)
Residual OFF
Residual ON
Fan (
∗
1)
ENTRY/
90 sec. timer starts.
∗
1. When the heater is ON, the airflow rate of the fan will be whichever is the largest between
the CFM dictated by the heater's own capacity, or the fan tap CFM determined by other
controls.
∗
2. Fan residual operation will continue, even if the indoor unit is turned off with the remote
controller operation button.
∗
1. External input ON is an input signal to the X1M-AIR CLEANER terminal on the PCB.
&
Fan operation at preset tap
(Fan tap can be changed by field setting
14 (24)-4.)
•
Remote control operation
(including thermostat OFF)
•
External input: ON (
∗
1)
∗
1. External input ON is an input signal to the X1M-HUMIDIFIER terminal on the PCB.
&
&
•
Remote control operation: ON
(including thermostat OFF)
•
When the external input
changes from ON to OFF.
•
Remote control operation: ON
(including thermostat OFF)
•
External input: ON (
∗
1)
Fan operation at preset tap
(Fan tap can be changed by field setting
14 (24)-4.)
Fan residual operation for 30 seconds
(Fan tap can be changed by field setting
14 (24)-4.)
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...