Troubleshooting by Error Code
SiUS372201EA
353
Part 6 Service Diagnosis
Reference
3.40 Electronic Expansion Valve Coil Abnormality or Sub PCB
Momentary Overcurrent
Applicable
Models
All outdoor unit models
Error Code
E9
Method of Error
Detection
Detects according to whether or not there is continuity across the electronic expansion valve coils.
Error Decision
Conditions
When no current flows through common (COM[+]) at the time of turning ON the power supply.
Supposed
Causes
Disconnection of connectors from electronic expansion valves
Defective electronic expansion valve coil
Defective outdoor unit main PCB
Sub PCB momentary overcurrent
Troubleshooting
CHECK 18
Refer to page 444.
Turn OFF the power supply
once, and then turn it ON again.
Return to normal?
Investigate external causes other than
failures (e.g. noise).
YES
NO
Connector for
the electronic expansion
valve of the outdoor unit
is connected.
Properly and securely connect the
connector.
NO
YES
Replace the electronic expansion
valve.
NO
Replace the outdoor unit main PCB
(A1P).
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check for electronic expansion valves applicable to the error code
E9
while in monitor mode.
Sub code
E9-01/05: Y1E (Master / Sub)
E9-03/06: Y2E (Master / Sub)
E9-04/07: Y3E (Master / Sub)
E9-26/27: Y4E (Master / Sub)
E9-29/34: Y5E (Master / Sub)
E9-11/12: Y6E (Master / Sub)
E9-30/35: Y7E (Master / Sub)
E9-31/36: Y8E (Master / Sub)
E9-57/58: Y6E, Y7E, Y8E (Master/Sub)
The
resistance of the
electronic expansion
valve coil is normal.
CHECK 18
YES
Replace the outdoor unit sub PCB
(A8P).
YES
Is the error code
E9-57/58?
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...