Troubleshooting by Error Code
SiUS372201EA
351
Part 6 Service Diagnosis
3.39 Outdoor Fan Motor Abnormality
Applicable
Models
All outdoor unit models
Error Code
E7
Method of Error
Detection
Detects according to the value of current flowing through the fan PCB.
Error Decision
Conditions
Overcurrent is detected from the fan PCB (Detecting overcurrent 4 times will shut down the
system).
Current does not increase at fan motor startup or while the fan motor is in operation (Detecting 4
times will shut down the system).
Supposed
Causes
Fan motor failure
Neglect to connect or defective connection of harness/connector between the fan motor and the
PCB
Fan does not rotate due to foreign matter caught in it.
Clearing condition: fan motor performs normal operation for a period of 5 minutes
Troubleshooting
There are
foreign matter around the
applicable fan.
Remove the foreign matter.
YES
Check for the connections of all fan motor connectors.
NO
Turn OFF the power supply, and then wait for a period of 10 minutes.
Some connectors are
disconnected.
Insert the connector.
YES
NO
NO
There is a relay
connection error.
Correct the connection of the
relay harness.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
A
Check for any wire connection errors in 2 fan motors.
M1F: Connectors are white both on the PCB side and motor side.
M2F: Connectors are white on the PCB side and red on the motor side.
Check for Connection of Connector
Check for Colors of Connectors
There is no
continuity across the fuse
(F101U) on the fan
PCB.
Replace the fan PCB.
YES
NO
For models equipped with 2 fan motors, check the fan motor
M1F or M2F applicable to the error code
E7
while in monitor
mode of the outdoor unit.
Check in Monitor Mode
Go to the next page.
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...