Troubleshooting by Error Code
SiUS372201EA
325
Part 6 Service Diagnosis
3.21 Transmission Abnormality between Indoor Unit Control
PCB and Fan PCB
Applicable
Models
FXSQ-TA, FXSQ-TB, FXMQ-PB, FXMQ-TB
Error Code
C1
Method of Error
Detection
Transmission conditions between the indoor unit control PCB (A1P) and fan PCB (A2P) are
checked via microcomputer.
Error Decision
Conditions
When normal transmission is not carried out for a certain duration.
Supposed
Causes
Connection defective the connector between indoor unit control PCB (A1P) and fan PCB (A2P)
Defective indoor unit control PCB (A1P)
Defective fan PCB (A2P)
External factor, such as instantaneous power failure