7.4 Outdoor Unit Rotation
In the case of multi outdoor unit system, this outdoor unit rotation prevents the compressor from
breaking down due to unbalanced oil level between outdoor units.
Details of outdoor unit rotation
In the case of multi outdoor unit system, each outdoor unit is given an operating priority for the
control.
The operating priority of outdoor units is changed by outdoor unit rotation. The outdoor unit rotation
prevents unbalanced oil level between outdoor units by eliminating the long stop of compressors
during partial load.
Timing of outdoor unit rotation
At the beginning of the startup control, or;
After oil return operation, or;
After defrost operation, or;
One of the outdoor units is stopped for 20 minutes or more (only in cooling).
Example) The following diagram shows outdoor unit rotation.
Master unit and sub unit in this section are the names for installation.
They are determined in installation work, and not changed thereafter. (These names are different
from master unit and sub unit for control.)
The outdoor unit connected the control wires (F1 and F2) for the indoor unit should be designated
as master unit.
Consequently, the LED display on the outdoor unit main PCB for master unit, sub unit does not
change.
Normal control
Normal control
Normal control
Normal control
Master
A
A
Startup control
Outdoor unit
rotation
Outdoor unit
rotation
Outdoor unit
rotation
Priority
1
Priority
1
Priority
2
Priority
2
Priority
1
Priority
2
Priority
2
Priority
1
Oil return operation
or defrost operation
Any of outdoor
unit stops for a
period of 20
minutes or more.
Sub
Master
Sub
Master
Sub
Master
Sub
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...