Special Control
SiUS372201EA
149
Part 4 Functions and Control
7.3 Defrost Operation
To defrost the outdoor heat exchanger while in Evaporator, the defrost operation is conducted to
recover the heating capacity.
Tb: Heat exchanger deicer temperature
REYQ72-168AA single system and REYQ192-240AA single system when outside temperature is lower than 0°C
(32°F)
Part name
Electric symbol
Function of functional part
Compressor motor
M1C, M2C
REYQ72AA: 127.3 rps
REYQ96/120AA: 125.4 rps + 140.0 rps
REYQ144/168AA: 85.2 rps + 114.9 rps
REYQ192/216/240AA: 135.0 rps + 140.0 rps
Fan motor
M1F, M2F
With high pressure
OFF ↔ Step X/2 ↔ Step X
Electronic expansion valve (Heat exchanger right upper)
Y1E
100%
Electronic expansion valve (Heat exchanger right lower)
Y2E
Electronic expansion valve (Heat exchanger left)
Y5E
Electronic expansion valve (Subcooling heat exchanger)
Y3E
Discharge temperature control
Electronic expansion valve (Receiver gas purge)
Y4E
Liquid recovery control
Electronic expansion valve (Refrigerant cooling IPM)
Y6E
Same as normal control
Electronic expansion valve (Refrigerant cooling air)
Y7E
Solenoid valve (Oil separator oil return)
Y1S, Y2S
ON
Solenoid valve (Liquid shutoff)
Y3S
ON
Solenoid valve (Accumulator oil return)
Y4S
ON
Solenoid valve (Refrigerant adjustment)
Y5S
OFF
Solenoid valve (Injection)
Y6S
ON
Four way valve (Heat exchanger right upper)
Y10S
OFF
Four way valve (Heat exchanger right lower)
Y7S
OFF
Four way valve (Heat exchanger left)
Y9S
OFF
Four way valve (HP/LP gas pipe)
Y8S
ON
Solenoid valve (Refrigerant cooling bypass)
Y11S
Same as normal control
Ending condition
A lapse of 15 minutes
Tb > 11°C (51.8°F) continues for 60 seconds or more
OR
Indoor unit actuator
Defrost operation
Fan
Thermostat ON unit
OFF
Non-operating unit
OFF
Thermostat OFF unit
OFF
Electronic expansion valve
Thermostat ON unit
Defrost EV opening degree
Non-operating unit
Defrost EV opening degree
Thermostat OFF unit
Defrost EV opening degree
Branch Selector unit actuator
Normal cooling
Normal simultaneous cooling/heating
Normal heating
Cooling
Heating
Electronic
expansion
valve (EVSC)
Y1E
Thermostat ON
0 pulse
0 pulse
Subcooling degree control
0 pulse
Non-operating
0 pulse
0 pulse
0 pulse
0 pulse
Thermostat OFF
0 pulse
0 pulse
0 pulse
0 pulse
Electronic
expansion
valve (EVH)
Y2E
Thermostat ON
6,000 pulse
0 pulse
6,000 pulse
6,000 pulse
Non-operating
6,000 pulse
0 pulse
6,000 pulse
6,000 pulse
Thermostat OFF
6,000 pulse
0 pulse
6,000 pulse
6,000 pulse
Electronic
expansion
valve (EVL)
Y3E
Thermostat ON
6,000 pulse
6,000 pulse
0 pulse
0 pulse
Non-operating
6,000 pulse
6,000 pulse
0 pulse
0 pulse
Thermostat OFF
6,000 pulse
6,000 pulse
0 pulse
0 pulse
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...