SiUS372201EA
Basic Control
Part 4 Functions and Control
130
5.2 Compressor PI Control
Carries out the compressor capacity PI control so that Te reaches the target value during cooling
and Tc during heating.
Controls compressor capacity to adjust Te to achieve target value (TeS).
1. VRT control (default)
When the indoor temperature approaches the set temperature in all indoor units and the
required capacity decreases, TeS is automatically increased to adjust the capacity.
2. Constant control
TeS is fixed to the set value.
Te setting
Te: Low pressure equivalent saturation temperature
TeS: Target temperature of Te (Varies depending on Te setting, operating frequency, etc.)
Controls compressor capacity to adjust Tc to achieve target value (TcS).
1. VRT control (default)
When the indoor temperature approaches the set temperature in all indoor units and the
required capacity decreases, TcS is automatically decreased to adjust the capacity.
2. Constant control
TcS is fixed to the set value.
Tc setting
Te: High pressure equivalent saturation temperature
TeS: Target temperature of Tc (Varies depending on Tc setting, operating frequency, etc.)
Branch Selector unit actuator
Normal cooling
Normal simultaneous cooling/heating
Normal heating
Cooling
Heating
Electronic
expansion
valve (EVSC)
Y1E
Thermostat ON
0 pulse
0 pulse
Subcooling degree
control
0 pulse
Non-operating
0 pulse
0 pulse
0 pulse
0 pulse
Thermostat OFF
0 pulse
0 pulse
0 pulse
0 pulse
Electronic
expansion
valve (EVH)
Y2E
Thermostat ON
6,000 pulse
0 pulse
6,000 pulse
6,000 pulse
Non-operating
6,000 pulse
0 pulse
6,000 pulse
6,000 pulse
Thermostat OFF
6,000 pulse
0 pulse
6,000 pulse
6,000 pulse
Electronic
expansion
valve (EVL)
Y3E
Thermostat ON
6,000 pulse
6,000 pulse
0 pulse
0 pulse
Non-operating
6,000 pulse
6,000 pulse
0 pulse
0 pulse
Thermostat OFF
6,000 pulse
6,000 pulse
0 pulse
0 pulse
Cooling
L
M
H
3°C
(37.4°F)
6°C
(42.8°F)
7°C
(44.6°F)
8°C
(46.4°F)
9°C
(48.2°F)
10°C
(50.0°F)
11°C
(51.8°F)
Heating
L
M
H
41°C
(105.8°F)
42°C
(107.6°F)
43°C
(109.4°F)
44°C
(111.2°F)
45°C
(113.0°F)
46°C
(114.8°F)
48°C
(118.4°F)
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...