S E R V I C E   M A N U A L

12000/18000 Btu/h Class

Outdoor Unit

Non-Inverter

Pair Type

Si01-983

Summary of Contents for RE12JV2S

Page 1: ...REMOVAL PROCEDURE S E R V I C E M A N U A L 12000 18000 Btu h Class Outdoor Unit Non Inverter Pair Type Si01 983...

Page 2: ...Service Manual Removal Procedure Outdoor Unit zCooling Only RE12JV2S RE18JV2S...

Page 3: ...ls Fan Motor 2 2 Removal of Electrical Components 10 3 Removal of Sound Blankets 14 4 Removal of Capillary Tube Pattern 1 15 5 Removal of Capillary Tube Pattern 2 16 6 Removal of Compressor ASSY 17 No...

Page 4: ...ssembling work Step Procedure Points 1 Appearance features Take care not to cut your finger by the fins of the outdoor heat exchanger 2 Remove the panels The stop valve cover is united with the shield...

Page 5: ...Panels Fan Motor Removal Procedure 3 2 Remove the 3 screws and remove the top panel 3 Remove the 4 screws and remove the discharge grille The discharge grille has 4 hooks Step Procedure Points Top pa...

Page 6: ...Fan Motor Si01 983 4 Removal Procedure 4 Remove the 8 screws and remove the front panel 5 Unfasten the hooks Pull and remove the front panel The front panel has 4 hooks Step Procedure Points R15228 F...

Page 7: ...reassembling 3 Pull out the 2 terminals red white from the fan capacitor C2R Fan capacitor C2R Terminal board X1M 4 Pull out the terminal black from the terminal board X1M 2 5 Release the fan motor l...

Page 8: ...motor fixing frame Put the fan motor lead wire through the back of the fan motor when reassembling so as not to be entangled with the outdoor fan When reassembling fit the lower hooks into the bottom...

Page 9: ...01 983 Removal of Outer Panels Fan Motor Removal Procedure 7 7 Release the fan motor lead wire from the hooks 8 Remove the 4 screws and remove the fan motor Step Procedure Points R15234 R15235 Fan mot...

Page 10: ...e right side panel 1 Remove the 3 screws and disconnect the connecting wire 2 Remove the screw and remove the wire clamp 3 Lift up and remove the guard net 4 Remove the 2 screws on the rear side Step...

Page 11: ...emove the 4 screws on the right side 6 Remove the screw near the connection port 7 Unfasten the hook of the right side panel When reassembling make sure to fit the hook 8 Remove the right side panel S...

Page 12: ...Step Procedure Points 1 Remove the nut and remove the terminal cover Preparation Remove the outer panels and disconnect the connector for the fan motor according to the Removal of Outer Panels Fan Mo...

Page 13: ...different by models Pattern 1 Step Procedure Points X11A X1M C2R C1R R10848 C2R X11A C1R R10849 X1M X1M 1 red White X11A C1R X1M 2 black X1M 1 Red R10850 R10851 Compressor R red Compressor S yellow C...

Page 14: ...ocedure Pattern 2 Step Procedure Points X11A K1M X2M X1M C1R C2R REC R10853 A2 5 4 A1 X1M 3 1 X2M C1R K1M 14 2 13 6 C2R F1S X11A REC R10854 C1R red yellow Compressor S Compressor R K1M 4 red R10855 C2...

Page 15: ...black X2M N white X1M 2 white C2 white R10857 X1M 2 green yellow Earth green yellow X1M 1 red X2M GRD X2M N X1M 3 black X2M N black X1M 3 K1M 3 black X2M L A A C2 white REC white Lower SECT A A X1M G...

Page 16: ...the sound blanket top Preparation Remove the outer panels according to the Removal of Outer Panels Fan Motor Remove the electrical components ASSY according to the Removal of Electrical Components AS...

Page 17: ...e refrigerant gas in the atmosphere Make sure to collect all the refrigerant gas Cautions for restoration 1 Restore the piping by non oxidation brazing 2 Avoid excessive heating Keep below 120 C In ca...

Page 18: ...frigerant gas in the atmosphere Make sure to collect all the refrigerant gas Cautions for restoration 1 Restore the piping by non oxidation brazing 2 Avoid excessive heating Keep below 120 C In case o...

Page 19: ...it for 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points 1 Remove the nut and remove the terminal cover 2 Disconnect the compressor lead wires S W...

Page 20: ...ions for restoration 1 Restore the piping by non oxidation brazing 2 Avoid excessive heating Keep below 120 C In case of difficulty with gas brazing machine 1 Disconnect the brazed part where is easy...

Page 21: ...Revision History Month Year Version Revised contents 02 2013 Si01 983 First edition...

Page 22: ...ies supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation of parts and acces...