17 .
Adjust refrigerant charge to obtain pressures indicated
.
18 .
Note weight of refrigerant tank.
19 .
When system has stabilized, check superheat at the
suction line service valve. The actual line temperature
should be 8° to 20°F higher than the saturation
temperature corresponding to the vapor pressure.
If superheat is measured at evaporator, the actual
line temperature should be 6° to 10° higher than the
saturation temperature corresponding to the vapor
pressure .
20 .
Close service ports on vapor and liquid valves. Remove
service gauges.
21 .
Replace service port caps and valve stem caps. These
caps must be replaced to prevent leaks.
22 .
Record total charge quantity on rating plate.
Final Leak Testing
After the unit has been properly evacuated and charged, a
halogen leak detector should be used to detect leaks in the
system. All piping within the condensing unit, evaporator, and
interconnecting tubing should be checked for leaks. If a leak is
detected, the refrigerant should be recovered before repairing
a the leak. The Clean Air Act prohibits releasing refrigerant into
the atmosphere .
Table 14: Charging Hints
Symptom
Possible Cause
Remedy
High head pressure
Air flow to/from condenser restricted or dirty condenser
Remove obstruction, relocate condensing unit,
if necessary clean condenser
Faulty condenser fan or motor
Replace
Overcharge of refrigerant
Reduce charge
Air in system
Evacuate and recharge
Low head pressure
Short of refrigerant
Check for leak, add charge
Low evaporator air flow
Increase blower speed, check filters
Low vapor & hot compressor
Short of refrigerant
Check for leak—add refrigerant
Excessive sweating
Low indoor airflow
Increase speed of air handler blower or reduce restriction,
replace air filter
Excess refrigerant
Slowly reduce charge
Table 15: Pre-Start Check
1
Is the condensing unit properly located and level?
Yes
No
2
Is there free air movement to and from the condensing unit?
Yes
No
3
Is the wiring connected according to the unit wiring diagram?
Yes
No
4
Are the wiring connections tight (including those in the unit and compressor electrical box)?
Yes
No
5
Is the unit properly grounded?
Yes
No
6
Is the circulating air blower correctly wired?
Yes
No
7
Is the condensing unit properly fused?
Yes
No
8
Is the thermostat level, correctly wired and in a good location?
Yes
No
9
Is the ductwork correctly sized, run, taped and insulated?
Yes
No
10
Is the refrigerant tubing neatly run and the vapor line thoroughly insulated?
Yes
No
11
Is the condensate drain properly sized, run, trapped and pitched?
Yes
No
12
Are the refrigerant connections tight and leak tested?
Yes
No
13
Are the filters clean and in place?
Yes
No
14
Does the condenser fan turn freely without rubbing?
Yes
No
15
Is the fan blade tight on the fan shaft?
Yes
No
16
Areall covers and access panels in place to prevent air loss?
Yes
No
IM 962-4 • AIR-COOLED SPLIT SYSTEM CONDENSERS
18
www.DaikinApplied.com
Installation
Summary of Contents for RCS Series
Page 35: ......