Outline of Control (Outdoor Unit) < Symbols using in this manual >
Si33-105
54
Function R407C PLUS Series Heat Recovery System
3.2.3
Standby due to Pe
!
Forcibly stops compressor operation just before detecting malfunction to prevent stopping
operation due to transitional drop of Pe. (Constrained automatic reset)
Contents
3.2.4
Standby due to Td
!
Forcibly stops compressor operation just before detecting malfunction to prevent stopping
operation due to transitional increase of Td. (Constrained automatic reset)
Contents
!
For 100 minutes after the first forced thermostat OFF under the above conditions, forced
thermostat OFF is conducted 2 times including the first. Third thermostat OFF is not
conducted. After 100 minutes elapsed after the first, the count turns to 0 repeating this
operation.
•
In compressor operation
•
Pe<0.03MPa
•
Not in oil return and defrosting operation
•
Elapsed time of 10 minutes or more after
oil return and defrosting operation
completion
•
Elapsed time of 10 minutes or more after
startup
•
Not in equalizing control
•
In oil return and defrost operation
•
Elapsed time of 10 minutes or less after oil
return and defrosting operation completion
•
Elapsed time of 10 minutes or less after startup
•
In pressure equalizing control
•
In compressor operation
•
Pe<0MPa
•
OR
→
•
Conducts forced thermostat OFF once
(turns to status of restart standby)
•
For 30 minutes after the first forced thermostat OFF under the above conditions, forced thermostat OFF
is conducted 2 times including the first. Third thermostat OFF is not conducted. After 30 minutes elapsed
after the first, the count turns to 0 repeating this operation.
&
&
&
(V2560)
I
OR
•
In compressor operation
•
HTdi or HTds>130˚C
→
•
Conducts forced thermostat OFF once
(turns to status of restart standby)
I
&
(V2561)
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...