List of Safety Device and Function Parts Setting Value
Si33-105
44
Function R407C PLUS Series Heat Recovery System
2. List of Safety Device and Function Parts Setting
Value
2.1
Outdoor Unit
Item
Name
Symbol
Model
RSEYP
16KJY1
RSEYP
18KJY1
RSEYP
20KJY1
RSEYP
24KJY1
RSEYP
26KJY1
RSEYP
28KJY1
RSEYP
30KJY1
Compressor
Inverter Compressor
M1C
JT236DCVTYE@2
STD Compressor 1
M2C
JT265DATYE@2
JT300DATYE@2
STD Compressor 2
M3C
—
—
—
JT300DATYE@2
Magnetic Relay (Inverter)
K1M
CLK-35J-P6
(STD)
K2M
HOE-35F-TRA1B
HOE-35F-TRA1D
20A
22A
(STD)
K3M
—
—
—
HOE-35F-TRA1D
22A
Crankcase Heater
E1~3HC
50W×2
50W×2
50W×2
50W×3
50W×3
50W×3
50W×3
Fan Motor
Fan Motor (Setting
temperature of
temperature switch)
M1F
140W
135±5°c
M2F
230W
135±5°c
M3F
140W
135±5°c
M4F
230W
135±5°c
M11F
—
—
—
140W
135±5°c
M12F
—
—
—
230W
135±5°c
M21F
—
—
—
140W
135±5°c
M22F
—
—
—
230W
135±5°c
Functional
Parts
Electronic Expansion
Valve
Y1E
Body : EDM-BA0YPDM-1
Coil : EBM-DM
Y2E
Body : EDM-BA0YPDM-1
Coil : EBM-DM
Body : EDM-BA0YPDM-1
Coil : EBM-DM
Y3E
—
Body : EDM-BA0YPDM-1
Coil : EBM-DM
Solenoid Valve
Y1S
(for Auxiliary condenser) NEV603DXF
Y2S
(for Hot gas) NEV603DXF
Y3S
(for Injection M1C) NEV202DXF
Y4S
(for receiver) NEV603DXF
Y5S
(for liquid pressure control) NEV202DXF
Y6S
(for Injection M2C) NEV202DXF
Y7S
—
—
—
(for Injection M3C) NEV202DXF
4 Way Valve
Y1~3R
VH60100
Pressure
Pressure Sensor
SENPH
PS8040A (0~3.33MPa)
SENPL
PS8040A (0~0.96MPa)
Pressure Switch
Q1·2PH
20PS688-10 OFF : 2.94
+0
–0.1
MPa
ON : 2.16±0.1MPa
Q3PH
—
—
—
20PS688-10 OFF : 2.94
+0
–0.1
MPa
ON : 2.16±0.1MPa
Pressure Regulating Valve
LRV(B)-3 MIN OPERATING PRESSURE 1.5~2.0 MPa
Thermistors
Thermistor (Ambient
temp.)
R1T
3.5~360k
Ω
(20k
Ω
at 25°C)
Thermistor (Coil)
R2T
3.5~360k
Ω
(20k
Ω
at 25°C)
Thermistor (Discharge)
R3T
3.5~400k
Ω
(20k
Ω
at 25°C)
Thermistor (header)
R4T
3.5~360k
Ω
(20k
Ω
at 25°C)
Thermistor (Suction pipe)
R6T
3.5~360k
Ω
(20k
Ω
at 25°C)
Thermistor (Liquid pipe)
R8T
3.5~360k
Ω
(20k
Ω
at 25°C)
Fuses
Fuse (A1P)
F1U·2U
AC250V, 10A
Fuse (A3P)
F1U
AC250V, 10A
Fuse (A4P)
F1U
—
—
—
AC250V, 10A
Fuse (Z1F)
F1U·2U
AC250V, 5A
Fusible Plug
Plug head melt at 70~75°C
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...