Test Operation
Si33-105
126
Test Operation R407C PLUS Series Heat Recovery System
1.12
Indoor Field Setting
Making a field setting
Field settings must be made by remote controller if optional accessories have been installed on
the indoor unit, or if the indoor unit or HRV unit’s individual functions have been modified.
1.12.1 Wired Remote Controller <BRC1A51>
1. When in the normal mode, push the
button for 4 seconds or more, and operation then
enters the “field set mode.”
2. Select the desired “mode No.” with the
button.
3. During group control and you want to set by each individual indoor unit (when mode No. 20,
21, 22, 23, 25 has been selected), push the time mode
button and select the “indoor
unit No.” to be set.
Note: This operation is not required when setting as a group.
4. Push the
button and select the first code No.
5. Push the
button and select the second code No.
6. Push the timer
button one time and “define” the currently set contents.
7. Push the
button to return to the normal mode.
(Example)
When setting the filter sign time to “Filter Dirtiness-High” in all group unit setting, set the Mode
No. to “10”, Mode setting No. to “0” and setting position No. to “02”.