Si33-105
Test Operation
Test Operation R407C PLUS Series Heat Recovery System
111
1.4.1
Setting Mode 1
The factory settings are:
Individual (C/H SELECT), OFF (L.N.O.P.), ON (SEQ. START)
You can change the cool/heat selection permission, low noise and
sequential start settings by pushing the SET switch.
To skip settings you don't want to change, push the RETURN switch
and go to the next setting.
Set cool/heat
selection to IND.
Change low noise operation to "ON".
External control adaptor for outdoor unit is required
if low noise operation is set to "ON".
Change sequential start to "OFF".
Setting complete
GROUP MASTER (cool/heat selection),
ON (low noise), OFF (sequential start)
MODE
TEST
L.N.O.P.
SEQ.
IND
MASTER SLAVE
START
H1P
H2P
H3P
H4P
H5P
H6P
H7P
SET
MODE
TEST
L.N.O.P.
SEQ.
IND
MASTER SLAVE
START
H1P
H2P
H3P
H4P
H5P
H6P
H7P
C/H SELECT
SET
MODE
TEST
L.N.O.P.
SEQ.
IND
MASTER SLAVE
START
H1P
H2P
H3P
H4P
H5P
H6P
H7P
C/H SELECT
MODE
TEST
L.N.O.P.
SEQ.
IND
MASTER SLAVE
START
H1P
H2P
H3P
H4P
H5P
H6P
H7P
C/H SELECT
SET
SET
MODE
TEST
L.N.O.P.
SEQ.
IND
MASTER SLAVE
START
H1P
H2P
H3P
H4P
H5P
H6P
H7P
C/H SELECT
MODE
TEST
L.N.O.P.
SEQ.
IND
MASTER SLAVE
START
H1P
H2P
H3P
H4P
H5P
H6P
H7P
C/H SELECT
SET
MODE
TEST
L.N.O.P.
SEQ.
IND
MASTER SLAVE
START
H1P
H2P
H3P
H4P
H5P
H6P
H7P
C/H SELECT
C/H
SELECT
SS1
IN/D
UNIT
OUT/D
UNIT
Cool/heat selection setting
(SS1)
(Factory set)
Do not set
RETURN
RETURN
RETURN
Monitor mode
MODE
Setting mode 2
MODE
Push and hold for 5 sec.
C/H SELECT
(VF133)
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...
Page 263: ...Si33 105 iv Index ...