11 Disposal

Installation manual

12

CVXM-A, FVXM-A, CVXM-A9, FVXM-A9, FVXTM-A

Split system air conditioners

3P477070-2P – 2022.09

1

In  cooling  mode,  select  the  lowest  programmable  temperature.
In heating mode, select the highest programmable temperature.
Test run can be disabled if necessary.

2

When  the  test  run  is  finished,  set  the  temperature  to  a  normal
level. In cooling mode: 26~28°C, in heating mode: 20~24°C.

3

The  system  stops  operating  3  minutes  after  the  unit  is  turned
OFF.

10.1.1

To perform a test run using the wireless
remote control

1

Press 

 to switch the system on.

2

Press the middle of 

 and 

 simultaneously.

3

Press 

 twice to choose 

 and confirm selection by pressing

.

Result: 

 on the display indicates that the test run is selected. Test

run operation will stop automatically after about 30 minutes.

4

To stop operation sooner, press the ON/OFF button.

11

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

12

Technical data

▪ A 

subset

  of  the  latest  technical  data  is  available  on  the  regional

Daikin website (publicly accessible).

▪ The 

full  set

  of  latest  technical  data  is  available  on  the  Daikin

Business Portal (authentication required).

12.1

Wiring diagram

Translation of wiring the diagram notes

On wiring diagram

Translation

Caution: When the main power is
turned OFF and then back on
again, operation will resume
automatically.

Caution: When the main power is
turned OFF and then back on
again, operation will resume
automatically.

Notice: (*) Applicable for units
with refrigerant leakage sensor
only.

Notice: (*) Applicable for units
with refrigerant leakage sensor
only.

12.1.1

Unified wiring diagram legend

For applied parts and numbering, refer to the wiring diagram on the
unit.  Part  numbering  is  by  Arabic  numbers  in  ascending  order  for
each part and is represented in the overview below by "*" in the part
code.

Symbol

Meaning

Symbol Meaning

Circuit breaker

Protective earth

Connection

Protective earth (screw)

Symbol

Meaning

Symbol Meaning

,

Connector

A

Rectifier

Earth

Relay connector

Field wiring

Short-circuit connector

Fuse

Terminal

INDOOR

Indoor unit

Terminal strip

OUTDOOR

Outdoor unit

Wire clamp

Residual current
device

Symbol

Colour

Symbol

Colour

BLK

Black

ORG

Orange

BLU

Blue

PNK

Pink

BRN

Brown

PRP, PPL

Purple

GRN

Green

RED

Red

GRY

Grey

WHT

White

SKY BLU Sky blue

YLW

Yellow

Symbol

Meaning

A*P

Printed circuit board

BS*

Pushbutton ON/OFF, operation
switch

BZ, H*O

Buzzer

C*

Capacitor

AC*, CN*, E*, HA*, HE*, HL*,
HN*, HR*, MR*_A, MR*_B, S*, U,
V, W, X*A, K*R_*, NE

Connection, connector

D*, V*D

Diode

DB*

Diode bridge

DS*

DIP switch

E*H

Heater

FU*, F*U, (for characteristics,
refer to PCB inside your unit)

Fuse

FG*

Connector (frame ground)

H*

Harness

H*P, LED*, V*L

Pilot lamp, light emitting diode

HAP

Light emitting diode (service
monitor green)

HIGH VOLTAGE

High voltage

IES

Intelligent eye sensor

IPM*

Intelligent power module

K*R, KCR, KFR, KHuR, K*M

Magnetic relay

L

Live

L*

Coil

L*R

Reactor

M*

Stepper motor

M*C

Compressor motor

M*F

Fan motor

M*P

Drain pump motor

M*S

Swing motor

MR*, MRCW*, MRM*, MRN*

Magnetic relay

N

Neutral

n=*, N=*

Number of passes through ferrite
core

PAM

Pulse-amplitude modulation

Summary of Contents for Perfera CVXM20A3V1B

Page 1: ...on manual Split system air conditioners English Installation manual Split system air conditioners CVXM20A3V1B FVXM25A3V1B FVXM35A3V1B FVXM50A3V1B CVXM20A3V1B9 FVXM25A3V1B9 FVXM35A3V1B9 FVXM50A3V1B9 FV...

Page 2: ...wiring diagram legend 12 1 About the documentation 1 1 About this document WARNING Make sure installation servicing maintenance repair and applied materials follow the instructions from Daikin includ...

Page 3: ...y connecting the piping to the indoor units DANGER RISK OF BURNING SCALDING CAUTION Incomplete flaring may cause refrigerant gas leakage Do NOT re use flares Use new flares to prevent refrigerant gas...

Page 4: ...Industries Czech Republic s r o declares that the radio equipment type inside of this unit is in compliance with Directive 2014 53 EU and S I 2017 1206 Radio Equipment Regulations 2017 This unit is c...

Page 5: ...m m is not listed below use the closest higher value The total refrigerant charge m the minimum floor area is Amin limitation depends also on room height H and if the unit is installed ABOVE or UNDER...

Page 6: ...ole location f Right bottom piping hole location 1 Drill a wall hole depending on which side piping is taken out See 5 2 2 To drill a wall hole 48 2 Open the front panel and remove the front grille 3...

Page 7: ...4 30 f 734 740 170 350 70 200 593 595 170 350 d e c c a A B mm a a 75 5 4 60 60 5 4 75 C 159 238 689 159 b b 0 6 75 75 5 4 h g 627 5 115 285 b b b b 300 5 3 Indoor unit installation drawing Half conce...

Page 8: ...ont grille same on the other side c Slit portion for side piping on the bottom frame same of the other side d Slit portion for the bottom piping 1 Cut off the slit portion using nippers 2 Remove an bu...

Page 9: ...ic acid deoxidised seamless copper for refrigerant piping INFORMATION Additional refrigerant charge is NOT allowed in case of combination of the outdoor unit 3MXM40 or 3MXM52 with the indoor units CVX...

Page 10: ...tact point gaps that provides full disconnection under overvoltage category III WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qualified p...

Page 11: ...n 1 After the drain piping refrigerant piping and the electrical wiring are finished Wrap the refrigerant pipes and the interconnection cable with insulation tape Overlap at least half the width of th...

Page 12: ...atically Caution When the main power is turned OFF and then back on again operation will resume automatically Notice Applicable for units with refrigerant leakage sensor only Notice Applicable for uni...

Page 13: ...S C Limit switch S L Float switch S NG Refrigerant leak detector S NPH Pressure sensor high S NPL Pressure sensor low S PH HPS Pressure switch high S PL Pressure switch low S T Thermostat S RH Humidi...

Page 14: ......

Page 15: ......