
3
|
Components
Service manual
71
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
A
Class 20~35 unit
a
Compressor wire terminals cover
a
A
A
Class 42~71 unit
a
Compressor wire terminals cover
a
a
Compressor wire terminals cover
5
Install the compressor insulation, see
55].
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
3.4 Damper motor
3.4.1 Checking procedures
To perform an electrical check of the damper motor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see