background image

 

O-UC12-FEB23-3 

Page 2 

 

Listen for any possible leaks and check all joints with 
bubble spray. If any leaks are discovered, release 
pressure slowly from system until empty, repair leak and 
then restart pressure testing procedure. Never attempt to 
repair a leak on a pressurized system. 

A strength test should also be incorporated according to local 
regulations. 

Once testing has been completed satisfactorily, release the 
pressure from the system gradually and safely to external 
atmosphere. 

Evacuation and Charging 

 

Moisture prevents proper functioning of the 
compressor and the refrigeration system. 
Ensure that a good quality vacuum pump is 
used to pull a minimum vacuum of 250 

microns (0.25 torr). 

Once pressure testing has been completed, the system can 
now be evacuated to remove air and any moisture from the 
piping. This can be done as follows: 

 

Ensure any nitrogen charge is safely released from the 
system. 

 

Connect a gauge manifold to the schrader connection of 
the unit.  

 

Connect a vacuum pump and vacuum gauge to the 
system. 

 

Evacuate the system until vacuum is below 250 microns 
(0.25 torr). 

 

Note: A triple evacuation procedure is recommended for all 
new systems or where moisture is suspected. 

Once the system is isolated and the vacuum pump is switched 
off, any rise in pressure indicates that either there may be a 
leak in the system or moisture is still present. In this case, 
recheck the system for leaks, repair as necessary, and then 
restart the evacuation procedure. Once completed 
satisfactorily, the vacuum pump and vacuum gauge can be 
removed. 

Drainage 

 

The evaporator drain pan fitting is supplied 
loose and must be fitted on site.  

Correct  fitting  is  vital  to  ensure  leak 

  free  operation.  The 

lock  nut  on  the  drain  fitting 

MUST

  be  fitted  the  right  way 

around;  otherwise,  it  will  not  tighten  against  the  drip  tray. 
One side of the nut has an angled recess 

 this must be facing 

towards  the  drip  tray.  The  fitting  does  not  require  any 
sealant, but a small amount of silicon sealant can be applied 

between the flared face of the fitting and the drip tray if so 
desired.  

The fitting 

is tied to the indoor unit’s fan guard and consists of:

 

 

1pcs aluminum alloy drain fitting 

3/4” BSP male thread

 

and  

 

1pcs hexagon locknut.  
 

To install the drain fitting, firstly unscrew the drain pan from 
the  indoor  unit.  Locate  the  drain  fitting  into  drain  pan, 
followed  with  locknut  to  secure  the  drain  fitting  to  the  drain 
pan.  Then  refit  the  drain  pan  to  the  unit.  Follow  diagram 
below to install the drain fitting in the correct way.   

 

The  locknut  only  requires  hand  tightening  and  then  pinching 
up with a spanner. Do not over tighten, else the threads may 
strip from the nut and damage the tray.   

Recommended minimum drainpi

pe diameter is 20mm or 3/4”. 

The drainpipe material could be either copper or plastic. It is 
not recommended to use flexible hose as it tends to kink 
easily which might cause blockage and water to back up in 
the unit. 

Drainpipe  must  be  leveled  to  permit  free  draining  of 
condensate from unit cooler.  

Drain traps need to be installed for trouble free operation. 
If  the  unit  cooler  is  operated  without  the 

drain  trap

,  warm 

air  with  higher  temperature  will  draw  from  outside  to  the 
cold room. Thus, warm air will significantly reduce the cooler 
capacity and may lead to ice formation in the drain pan. 
If  the  temperature  surrounding  the  drain  line  and  trap  is 
below freezing (0

o

C), it must be wrapped with a drain line 

heater. Drain pan coupling and drainpipe must be insulated 
up to the external wall surface of the cool room. Make sure 
the  drain  pan  and  drain  line  is  free  from  debris  to  avoid 
clogging and cause overflowing. 
 

 

 

Summary of Contents for O-UC12-FEB23-3

Page 1: ...3 Low Temperature Scan below QR code to download latest manual from Website https drm daikinmalaysia com download AIR COOLED COMMERCIAL REFRIGERATION SLIM UNIT COOLER INSTALLATION MAINTENANCE IOM NO O...

Page 2: ...task in question SAFETY SYMBOLS The following symbols are used in this document to alert the reader to specific situations WARNING Warning Risk of serious injury or death to person CAUTION Caution Da...

Page 3: ...Wave with fins spacing 5mm copper bare tubes with nominal diameter of 10mm This fins pattern stands out for better performance of air flow and heat transfer Superheat measurement air tightness test a...

Page 4: ...mm 12 7 12 7 Nominal capacities are rated in accordance with EN 328 SC3 wet coil condition for R404A with TD 7K Sound Pressure Level is measured at 1m away from every side of the unit and 1m below fa...

Page 5: ...0 95 1 1 LFSLHS0300AXV1 1 1 1 0 95 1 1 TD Correction Factor To calculate cooling capacity for different temperature difference multiply the cooling capacity obtained from section 2 2 2 with respectiv...

Page 6: ...e identified and operatives have suitable PPE Ensure the working area has adequate ventilation during brazing procedures The units contain moving machinery and electrical power hazards which may cause...

Page 7: ...ting and ensure only superheated vapor is returned to compressor suction Adequately support all pipe work at a maximum of 2 meter intervals Pressure testing The unit cooler has been pressure tested in...

Page 8: ...the drain fitting MUST be fitted the right way around otherwise it will not tighten against the drip tray One side of the nut has an angled recess this must be facing towards the drip tray The fittin...

Page 9: ...with longer length as shown in below diagram Cable type and sizing must be selected for the application and the electrical installation should conform to the current local standards The power cable to...

Page 10: ...y in room Limit access to cold room do not keep doors open during stocking Accumulation of ice or water in drain pan Drain line plugged Clean drain line Make sure drain line is insulated properly Drai...

Page 11: ...O UC12 FEB23 3 Page 2 Wiring Diagram LFSLHS0200AXV1 LFSLHS0300AXV1...

Page 12: ...ON MALAYSIA SDN BHD 34543 W Shah Alam Plant 11A Jalan Utas 15 7 Seksyen 15 40200 Shah Alam Selangor Malaysia Banting Plant Lot 10 Jalan Perusahaan 8 Kawasan Perusahaan Pekan Banting 42700 Banting Sela...

Reviews: