16
|
Disposal
Installer reference guide
70
4MWXM-A9
R32 Split series
4P708645-1 – 2022.09
16 Disposal
NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of
the refrigerant, oil and other parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for reuse, recycling and recovery.
16.1 Overview: Disposal
Typical workflow
Disposing of the system typically consists of the following stages:
1
Pumping down the system.
2
Bringing the system to a specialized treatment facility.
INFORMATION
For more details, see the service manual.
16.2 To pump down
Example:
To protect the environment, pump down when relocating the unit or
when disposing of the unit.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage.
If you want to pump down the system, and there
is a leak in the refrigerant circuit:
▪
Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit.
Possible consequence:
Self-
combustion and explosion of the compressor because of air going into the
operating compressor.
▪
Use a separate recovery system so that the unit's compressor does NOT have to
operate.
NOTICE
During pump down operation, stop the compressor before removing the refrigerant
piping. If the compressor is still running and the stop valve is open during pump
down, air will be sucked into the system. Compressor breakdown or damage to the
system can result due to abnormal pressure in the refrigerant cycle.
Pump down operation will extract all refrigerant from the system into the outdoor
unit.
1
Remove the valve cap from the both liquid stop valves and the both gas stop
valves.
2
Carry out forced cooling. See
"16.3 To start and stop forced cooling"
3
After 5 to 10 minutes (after only 1 or 2 minutes in case of very low ambient
temperatures (<−10°C)), close the both liquid stop valves with a hexagonal
wrench.
4
Check on the manifold if the vacuum is reached.
Summary of Contents for Multi+ R32 Split Series
Page 1: ...Installer reference guide R32 Split series 4MWXM52A2V1B9...
Page 31: ...6 Unit installation Installer reference guide 31 4MWXM A9 R32 Split series 4P708645 1 2022 09...
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ...4P708645 1 2022 09 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...