![Daikin Multi+ R32 Split Series Installer'S Reference Manual Download Page 24](http://html1.mh-extra.com/html/daikin/multi-r32-split-series/multi-r32-split-series_installers-reference-manual_4701102024.webp)
6
|
Unit installation
Installer reference guide
24
4MWXM-A9
R32 Split series
4P708645-1 – 2022.09
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a well-
ventilated room without continuously operating ignition sources (e.g. open flames,
an operating gas appliance, or an operating electric heater). The room size shall be as
specified in the General safety precaution.
6.1.1 Installation site requirements of the outdoor unit
INFORMATION
Also read the following requirements:
▪
"2 General safety precautions"
7].
▪
"7.1.3 Refrigerant piping length and height difference"
33].
Mind the following spacing guidelines:
>100
>50
>350
(mm)
b
a
>100
>50
b
a
>100
b
a
b
a
>350
>350
>50
b
a
≤1200
>100
>350
a
b
a
Air outlet
b
Air inlet
Allow 300 mm of work space below the ceiling surface and 250 mm for piping and
electrical servicing.
>250
>300
(mm)
NOTICE
▪
Do NOT stack the units on each other.
▪
Do NOT hang the unit on a ceiling.
Strong winds (≥18 km/h) blowing against the outdoor unit’s air outlet causes short
circuit (suction of discharge air). This may result in:
▪
deterioration of the operational capacity;
▪
frequent frost acceleration in heating operation;
Summary of Contents for Multi+ R32 Split Series
Page 1: ...Installer reference guide R32 Split series 4MWXM52A2V1B9...
Page 31: ...6 Unit installation Installer reference guide 31 4MWXM A9 R32 Split series 4P708645 1 2022 09...
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ...4P708645 1 2022 09 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...