background image

Daikin

 IM 1019

3

Installation Instructions

Installation Instructions

Applications and features

For 2 or 4 Pipe Fan Coil and On/Off Control Applications

• 7 Day, 4 Event Programmability

• System Selection: Off-Heat-Cool-Auto-Setback

• 6 Outputs: 1H, 1C, Up to 3 Fan, OA Damper

• Fan Control: 1-3 Speeds

- Cycling (Auto) or Continuous (On)

- Automatic Fan Speed Staging (TB180 models only)

Connections for:

• Fan Coil Pipe Sensor

• Remote Temperature Probe

• Occupancy Control

• Door Switch or Setback

• Condensate Overflow

Specifications

Figure 1: MT180 Programmable Thermostat Dimensions 

WARNING

READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE
THIS THERMOSTAT.

Failure to observe safety information and comply with
instructions could result in PERSONAL INJURY, DEATH
AND/OR PROPERTY DAMAGE.

To avoid electrical shock or damage to equipment,
disconnect power before installing or servicing and use only 
wiring with insulation rated for full thermostat operating
voltage.

Before installing this control, the Voltage Selection Switch
must be placed in the correct position. See instructions.

To avoid potential fire and/or explosion do not use in
potentially flammable or explosive atmospheres.

Retain these instructions for future reference. This product,
when installed, will be part of an engineered system whose
specifications and performance characteristics are not
designed or controlled by PECO. You must review your
application and national and local codes to assure that your 
installation will be functional and safe.

CAUTION

Use copper wire only, insulate or wire nut all unused leads.

Care should be used to avoid electrostatic discharge to the
T180 thermostat.

This unit has configuration jumpers. You may need to
reconfigure this thermostat for your application

Table 1: MT180 Programmable Thermostat Specifications

Temperature 

Set Point Range

50 to 90°F / 10 to 32°C

Differential

Memory – Back-Up

EEPROM, No batteries required, 
Stores settings for unlimited time

Mounting

Installs on standard 4" x 4" device box 
with a 2" x 4" horizontal mud ring

Physical Dimensions

4.4"H x 5.8"W x 1.1"D

Agency Approvals

UL, UL Canada

Electrical Ratings

(see Ratings table)

Summary of Contents for MT 180

Page 1: ...Installation and Maintenance Manual IM 1019 Group Fan Coil Part Number IM 1019 Date October 2011 2011 Daikin MT 180 Programmable Thermostat...

Page 2: ...Program 10 System Check out 11 Condensate Overflow Interrupt 11 Thermostat configuration Service Menu 11 Technical and Application Notes 12 Fan Operation 12 Standard Fan Operation 12 Staged Fan Opera...

Page 3: ...installing this control the Voltage Selection Switch must be placed in the correct position See instructions To avoid potential fire and or explosion do not use in potentially flammable or explosive...

Page 4: ...n offers two different 7 Day Programmable Digital Heating Cooling Thermostat with constant fan or Fan cycled On Off Valve Control depending on the fan speed control used See Table 2 Table 2 Thermostat...

Page 5: ...s for further information on Pipe Sensor Operation page 12 2 Pipe Operation Install JP4 The thermostat will per manently disable the Secondary Output and disables sys tem and fan invalid modes 4 Pipe...

Page 6: ...off the entire system SETBACK Indicates the heating or cooling system is operating in setback mode Setback mode is an energy saving feature that can be either manually activated by the thermostat s u...

Page 7: ...o the ther mostat s default display Up Down Arrow Button Operation The and buttons function in two ways When you are in the default display you can press to increase or to decrease the current tempera...

Page 8: ...e factory default or installer selected during installation During setback mode when a demand for heating or cooling exists the fan will run at the lowest speed Automatic setback mode If your thermost...

Page 9: ...ctory program meets your needs simply follow the Setting the Clock Day instructions and you re done If you want to change the preprogrammed times and or temperatures follow the instructions under Cust...

Page 10: ...ect DAY Program the Evening period for SASU by repeating steps 1 through 8 but in Step 4 select EVE Program the Sleep period for SASU by repeating steps 1 through 8 but in Step 4 select SLEEP Now you...

Page 11: ...terrupt The remote probe input can be used with a condensate overflow interrupt switch CO either in conjunction with a remote probe normally closed CO switch or with local sensing normally open CO swi...

Page 12: ...a purge cycle if the sensed water temperature is ambiguous not adequately hot or cold The purge cycle algorithm can be either temperature or time based depending on the configuration of Service Menu...

Page 13: ...stat outputs are disabled for 1 hour After 1 hour the purge cycle resumes at step 1 HVACSetback Systems Setback Operation Remove JP3 This is a low level input that is normally open When switch is clos...

Page 14: ...trol of a guest room HVAC system It incorporates an innovative dual delay processor which allows the sensor to verify the nature of occupancies and is capable of eliminating unnecessary actuations of...

Page 15: ...cy status detection If the sensor determines that a room is occupied it will allow normal HVAC control The sensor will wait for another door open signal before determining occupancy again In an unoccu...

Page 16: ...d Start Time Heat Setpoint Temperature Cool Setpoint Temperature Monday Wake Day Evening Sleep Tuesday Wake Day Evening Sleep Wednesday Wake Day Evening Sleep Thursday Wake Day Evening Sleep Friday Wa...

Page 17: ...urge Cycle 0 Time Based Default 1 Temperature Based Determines if the Purge Cycle will be Temperature or Time Based 17 Minimum Dead Band Adjustment 3 F Default 3 10 F 1 5 5 C A changeover deadband val...

Page 18: ...Training Department Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty...

Reviews: