background image

Daikin

 IM 1019

15

Optional Occupancy Detection Equipment Operation

SD200-001 Occupancy Sensor

The SD200-001 occupancy sensor (

Figure 12

serves as a 

master sensor for a guest room HVAC management system. 
The sensor provides HVAC operation according to occupancy 
status, as well as door/window switch monitoring, selectable 
high/low temperature setback, form-C output, slave sensor 
connectivity, and a five minute door open HVAC shut-off.

Note: 

To use this configuration, the jumper to JP3 is 
removed to allow setback input.

Note: 

An optional door and/or window switch (

Figure 12

and slave sensor can be added for use with the 
SD200-001 sensor.

Operation

In an occupied mode, the SD200-001 occupancy sensor 
(

Figure 12

) and door switch use advanced microprocessor 

logic to determine occupancy. A door open signal will initiate 
occupancy status detection. If the sensor determines that a 
room is occupied, it will allow normal HVAC control. The 
sensor will wait for another door open signal before 
determining occupancy again.

In an unoccupied mode, the sensor continually monitors the 
room. Any occupancy detection will set the operation to 
occupied mode.

Figure 12: Optional equipment configuration #2 

SD200-002 Occupancy Sensor

The SD200-002 occupancy sensor serves as a stand alone 
master sensor for a guest room HVAC management system.

The sensor provides HVAC operation according to occupancy 
status, as well as selectable high/low temperature setback, 
form-C output, and a five minute door open HVAC shut-off.

This system provides basic room setback and is ideal for 
control of HVAC in commercial spaces.

Note: 

Note – To use this configuration, the jumper to JP3 is 
removed to allow setback input.

Operation

With each occupancy detection, an OFF delay is started and 
can be set to delay for up to 30 minutes (

Figure 13

).

Figure 13: Optional equipment configuration #3

Summary of Contents for MT 180

Page 1: ...Installation and Maintenance Manual IM 1019 Group Fan Coil Part Number IM 1019 Date October 2011 2011 Daikin MT 180 Programmable Thermostat...

Page 2: ...Program 10 System Check out 11 Condensate Overflow Interrupt 11 Thermostat configuration Service Menu 11 Technical and Application Notes 12 Fan Operation 12 Standard Fan Operation 12 Staged Fan Opera...

Page 3: ...installing this control the Voltage Selection Switch must be placed in the correct position See instructions To avoid potential fire and or explosion do not use in potentially flammable or explosive...

Page 4: ...n offers two different 7 Day Programmable Digital Heating Cooling Thermostat with constant fan or Fan cycled On Off Valve Control depending on the fan speed control used See Table 2 Table 2 Thermostat...

Page 5: ...s for further information on Pipe Sensor Operation page 12 2 Pipe Operation Install JP4 The thermostat will per manently disable the Secondary Output and disables sys tem and fan invalid modes 4 Pipe...

Page 6: ...off the entire system SETBACK Indicates the heating or cooling system is operating in setback mode Setback mode is an energy saving feature that can be either manually activated by the thermostat s u...

Page 7: ...o the ther mostat s default display Up Down Arrow Button Operation The and buttons function in two ways When you are in the default display you can press to increase or to decrease the current tempera...

Page 8: ...e factory default or installer selected during installation During setback mode when a demand for heating or cooling exists the fan will run at the lowest speed Automatic setback mode If your thermost...

Page 9: ...ctory program meets your needs simply follow the Setting the Clock Day instructions and you re done If you want to change the preprogrammed times and or temperatures follow the instructions under Cust...

Page 10: ...ect DAY Program the Evening period for SASU by repeating steps 1 through 8 but in Step 4 select EVE Program the Sleep period for SASU by repeating steps 1 through 8 but in Step 4 select SLEEP Now you...

Page 11: ...terrupt The remote probe input can be used with a condensate overflow interrupt switch CO either in conjunction with a remote probe normally closed CO switch or with local sensing normally open CO swi...

Page 12: ...a purge cycle if the sensed water temperature is ambiguous not adequately hot or cold The purge cycle algorithm can be either temperature or time based depending on the configuration of Service Menu...

Page 13: ...stat outputs are disabled for 1 hour After 1 hour the purge cycle resumes at step 1 HVACSetback Systems Setback Operation Remove JP3 This is a low level input that is normally open When switch is clos...

Page 14: ...trol of a guest room HVAC system It incorporates an innovative dual delay processor which allows the sensor to verify the nature of occupancies and is capable of eliminating unnecessary actuations of...

Page 15: ...cy status detection If the sensor determines that a room is occupied it will allow normal HVAC control The sensor will wait for another door open signal before determining occupancy again In an unoccu...

Page 16: ...d Start Time Heat Setpoint Temperature Cool Setpoint Temperature Monday Wake Day Evening Sleep Tuesday Wake Day Evening Sleep Wednesday Wake Day Evening Sleep Thursday Wake Day Evening Sleep Friday Wa...

Page 17: ...urge Cycle 0 Time Based Default 1 Temperature Based Determines if the Purge Cycle will be Temperature or Time Based 17 Minimum Dead Band Adjustment 3 F Default 3 10 F 1 5 5 C A changeover deadband val...

Page 18: ...Training Department Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty...

Reviews: