background image

12

Daikin

 IM 1019

Technical and Application Notes

Technical and Application Notes

Fan Operation

The thermostat may be factory configured for standard or 
staged fan operation.

Standard Fan Operation 

Single setpoint represented in 

Figure 9

. Programming mode 

includes multiple setpoints. 

Staged Fan Operation with Temperature Demand 

Single setpoint represented in 

Figure 10

. Programming mode 

includes multiple setpoints.

Figure 9: Standard Fan Operation 

Figure 10: Staged Fan Operation

Fancoil Operation

Fancoil operation is either a 2-pipe or 4-pipe configuration 
which is determined by jumper selection JP4 (see 

Installing, 

Mounting and Wiring the Thermostat‚ page 4

).

Pipe Sensor Operation 

A pipe sensor can be connected when the thermostat is 
configured for either 2-pipe or 4-pipe fan coil operation (see 
JP4 jumper configuration). The Pipe sensor is used to 
determine the water temperature in the Main Coil. The Pipe 
Sensor should be mounted on the Main Coil supply and 
wrapped with insulating material. 

Pipe Sensor Input: 10K Remote Probe or a standard On-Off 
Aqua-stat can be used for summer/winter changeover. ON 
(closed) is winter heating mode and OFF (open) is summer 
cooling mode.

Purge Cycle Operation 

With a pipe sensor connected, this thermostat will initiate a 
purge cycle if the sensed water temperature is ambiguous (not 
adequately hot or cold). The purge cycle algorithm can be 
either temperature or time based, depending on the 
configuration of Service Menu 16.

Temperature-Based Purge 

When an Ambiguous mode is detected and a demand exists,
a 3 minute purge timer begins and the Main Output is 
opened.

After the 3 minute purge cycle, the thermostat checks again
to see if the water temperature is more than 15°F from set 
point, or above 80°F or below 60°F.

If Winter or Summer mode is determined, normal HVAC
operation occurs. If still ambiguous, the thermostat checks to 
see if the COIL temperature is below 60°F or above 80°. 

Coil < 60°F = Summer Mode. 
Coil > 80°F = Winter mode.

Purge Cycle is repeated until a non-ambiguous condition is
sensed.

Note: 

If at any time the demand goes away, the thermostat will 
abort the purge cycle.

Table 16: Standard Fan Operation Overview

Menu

Description

FAN ON

Fan is on continuously and is not dependant on 
a heat or cool demand

FAN AUTO

Fan cycles on with a heat or cool temperature 
demand and cycles off with the heat or cool 
output

FAN SPEED

High, medium, or low is selected by the user

Table 17: Staged Fan Operation with Temperature Demand 
Overview

Menu

Description

FAN ON

Fan stages from high to medium to low and 
stays continuously on in the lowest available 
speed

FAN AUTO

Fan stages from high to medium to low and 
cycles off at set point

FAN SPEED

selected by the thermostat program

Summary of Contents for MT 180

Page 1: ...Installation and Maintenance Manual IM 1019 Group Fan Coil Part Number IM 1019 Date October 2011 2011 Daikin MT 180 Programmable Thermostat...

Page 2: ...Program 10 System Check out 11 Condensate Overflow Interrupt 11 Thermostat configuration Service Menu 11 Technical and Application Notes 12 Fan Operation 12 Standard Fan Operation 12 Staged Fan Opera...

Page 3: ...installing this control the Voltage Selection Switch must be placed in the correct position See instructions To avoid potential fire and or explosion do not use in potentially flammable or explosive...

Page 4: ...n offers two different 7 Day Programmable Digital Heating Cooling Thermostat with constant fan or Fan cycled On Off Valve Control depending on the fan speed control used See Table 2 Table 2 Thermostat...

Page 5: ...s for further information on Pipe Sensor Operation page 12 2 Pipe Operation Install JP4 The thermostat will per manently disable the Secondary Output and disables sys tem and fan invalid modes 4 Pipe...

Page 6: ...off the entire system SETBACK Indicates the heating or cooling system is operating in setback mode Setback mode is an energy saving feature that can be either manually activated by the thermostat s u...

Page 7: ...o the ther mostat s default display Up Down Arrow Button Operation The and buttons function in two ways When you are in the default display you can press to increase or to decrease the current tempera...

Page 8: ...e factory default or installer selected during installation During setback mode when a demand for heating or cooling exists the fan will run at the lowest speed Automatic setback mode If your thermost...

Page 9: ...ctory program meets your needs simply follow the Setting the Clock Day instructions and you re done If you want to change the preprogrammed times and or temperatures follow the instructions under Cust...

Page 10: ...ect DAY Program the Evening period for SASU by repeating steps 1 through 8 but in Step 4 select EVE Program the Sleep period for SASU by repeating steps 1 through 8 but in Step 4 select SLEEP Now you...

Page 11: ...terrupt The remote probe input can be used with a condensate overflow interrupt switch CO either in conjunction with a remote probe normally closed CO switch or with local sensing normally open CO swi...

Page 12: ...a purge cycle if the sensed water temperature is ambiguous not adequately hot or cold The purge cycle algorithm can be either temperature or time based depending on the configuration of Service Menu...

Page 13: ...stat outputs are disabled for 1 hour After 1 hour the purge cycle resumes at step 1 HVACSetback Systems Setback Operation Remove JP3 This is a low level input that is normally open When switch is clos...

Page 14: ...trol of a guest room HVAC system It incorporates an innovative dual delay processor which allows the sensor to verify the nature of occupancies and is capable of eliminating unnecessary actuations of...

Page 15: ...cy status detection If the sensor determines that a room is occupied it will allow normal HVAC control The sensor will wait for another door open signal before determining occupancy again In an unoccu...

Page 16: ...d Start Time Heat Setpoint Temperature Cool Setpoint Temperature Monday Wake Day Evening Sleep Tuesday Wake Day Evening Sleep Wednesday Wake Day Evening Sleep Thursday Wake Day Evening Sleep Friday Wa...

Page 17: ...urge Cycle 0 Time Based Default 1 Temperature Based Determines if the Purge Cycle will be Temperature or Time Based 17 Minimum Dead Band Adjustment 3 F Default 3 10 F 1 5 5 C A changeover deadband val...

Page 18: ...Training Department Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty...

Reviews: