ESIE19-06
|
Part 3. Repair
3.2. Unit specific repair procedures
21/01/20
|
Version 1.1
Page 45
Modular L Smart
3.2.1.4. Basic removal - removing doors and central panel
PRELIMINARY ACTIONS
1. Switch off the Daikin unit via the user interface.
2. Switch off the Daikin unit with the field supplied circuit breaker.
PROCEDURE
Removal
1. Loosen the 16 screws of the doors and central panel.
2. Take the doors off.
3. Loosen the 4 drain panel screws.
4. Disconnect the syphon for consedate.
5. Take the central panel off.
Figure 3-4: Removing doors and central panel