SiSG121917E
Code Indication on Remote Controller
Part 6 Service Diagnosis
114
4. Code Indication on Remote Controller
4.1 Indoor Unit
Wall mounted and LSP duct type
MSP duct type
In general, the error codes display automatically and system stops. Inspect and repair the error.
: “Inspection” is not displayed. The system operates, but be sure to inspect and repair the
error.
Error Codes
Description
Reference Page
00
Normal condition
—
A1
Indoor unit PCB abnormality
A5
Freeze-up protection control
A6
Indoor fan motor or related
abnormality
DC motor (CTKS, CTKB
series)
AC motor (FDKS series)
C4
Indoor heat exchanger thermistor or related abnormality
C9
Room temperature thermistor or related abnormality
U4
Signal transmission error (between indoor unit and outdoor
unit)
UA
Unspecified voltage (between indoor unit and outdoor unit)
Error Codes
Description
Reference Page
00
Normal condition
—
A1
Indoor unit PCB abnormality
A3
Drain water level control system abnormality
A6
Fan motor or related abnormality
DC motor (FDMR series)
A8
Fan PCB abnormality
AF
Drain system abnormality
C4
Indoor heat exchanger thermistor or related abnormality
C5
Indoor heat exchanger thermistor or related abnormality
C9
Room temperature thermistor or related abnormality
CJ
Remote controller thermistor abnormality
U5
Signal transmission error (between indoor unit and remote
controller)
U8
Signal transmission error (between MAIN remote controller
and SUB remote controller)
UA
Field setting abnormality