BACNET DATA TABLES
MT2300 WSHP BACNET INTEGRATION
DAIKIN APPLIED
16
Table 5: Binary Inputs, Continued
Point Name
Object
Type/
Instance
BACnet Object
Name
Range
Description
Compressor Dual Speed
Option
(SmartSource Series2)
BI:34
IO_ConfigSw10
0 = Off
1 = On
Indicates the compressor type configured for the unit. Applies to SmartSource
Series2 application .
0 = Off: Single speed compressor
1 = On: Dual speed compressor
Lead Compressor Select
Option
(SmartSource SS2C)
Indicates the lead compressor selection configured for the unit. Applies to
SmartSource SS2C application .
0 = Off: Compressor 1 is lead
1 = On: Compressor 2 is lead
Humidistat Input
BI:35
Humidistat
0 = Inactive
1 = Active
Indicates the status of the humidistat signal . The thermsostat uses this input
when dehumidification or waterside economizer is required. The network variable
(MSV:16) overrides the humidistat input .
1
This switch is effective only when the network scheduling is not in use.
Table 6: Binary Outputs
Point Name
Object
Type/
Instance
BACnet Object
Name
Read/
Write
Access
Description
Thermostat Alarm
BO:1
Alarm
R
Thermostat alarm output status .
0 = Alarm output command is Off (0 VAC)
1 = Alarm output command is On (24 VAC)
Compressor 1
BO:2
Comp1Out
R
Compressor 1 output command status .
0 = Compressor 1 command is Off
1 = Compressor 1 command is On
Fan Main Enable
BO:3
FanMainOut
R
Fan main enable output command status .
0 =
Fan main command is Off
1 = Fan main command is On
Fan Speed
BO:4
FanLowOut
R
Fan speed output command status . Applies only when the Fan Main output command
is On .
0 = Fan high speed command is On
1 = Fan low speed command is On
Pump Request
BO:5
PumpOut
R
Pump output command status for loop fluid flow.
0 = Pump command is Off
1 = Pump command is On
Reversing Valve 1
BO:6
RevVlv1Out
R
Compressor 1 reversing valve output command status .
0 = Reversing valve 1 command is Off (cooling)
1 = Reversing valve 1 command is On (heating)
Compressor 2 / Compressor
High Capacity
BO:7
Comp2Out
R
Compressor 2 output command status .
0 = Compressor 2 command is Off
1 = Compressor 2 command is On
Reversing Valve 2
BO:8
RevVlv2Out
R
Compressor 2 reversing valve output command status .
0 = Reversing valve 2 command is Off (cooling)
1 = Reversing valve 2 command is On (heating)
Auxiliary Heat 1
BO:9
AuxHeat1Out
R
Auxiliary heat 1 output command status. Applies when unit is configured to use
supplemental electric heat, boilerless electric heat, or hydronic heating .
0 = Electric heat 1 command is Off
1 = Electric heat 1 command is On
Auxiliary Heat 2
BO:10
AuxHeat2Out
R
Auxiliary heat 2 output command status. Applies when unit is configured to use
supplemental electric heat or boilerless electric heat .
0 = Electric heat 2 command is Off
1 = Electric heat 2 command is On
Hot Gas Reheat
BO:11
HGR_Out
R
Hot gas reheat (HGR) output command status .
0 = HGR command is Off (valve is closed)
1 = HGR command is On (valve is open)
Waterside Economizer
BO:12
WSE_Out
R
Waterside economizer (WSE) output command status .
0 = WSE command is Off (valve is closed)
1 = WSE command is On (valve is open)