Troubleshooting
ERROR CODE: P1 – Inverter Over-Ripple Protection
Remote
Controller
Display
P1
Method of
Malfunction
Detection
Imbalance in supply voltage is detected in PC board .
Imbalance in the power supply voltage causes increased ripple of voltage of the main
circuit capacitor in the inverter. Consequently, the increased ripple is detected.
Malfunction
Decision
Condition
“
P1
” will be displayed by pressing the inspection button .
When the amplitude of the ripple exceeding a certain value is detected for consecutive 4
minutes .
Supposed
Causes
●
Open phase
●
Voltage imbalance between phases
●
Defect of main circuit capacitor
●
Defect of inverter PC board
●
Defect of K2 relay in inverter PC board
●
Improper main circuit wiring