ERROR CODE: L4 – Malfunction of Inverter Radiating Fin Temperature Rise
Remote
Controller
Display
L4
Method of
Malfunction
Detection
Fin temperature is detected by the thermistor of the radiation fin.
Malfunction
Decision
Condition
When the temperature of the inverter radiation fin increases above 188.6°F.
Supposed
Causes
● Actuation of fin thermal (Actuates above 188.6°F)
●
Defect of inverter PC board
● Defect of fin thermistor