Determining Cooling Status
Clg Status is a status item which indicates whether or not
mechanical cooling is currently allowed . If cooling is disabled,
the reason is indicated .
The following are descriptions of cooling status states .
Enabled
Mechanical cooling is enabled if all the following are true:
• Control mode is not set via the keypad to fan only or heat
only
• Control mode is set via the keypad to auto and not
disabled via a third-party signal
• The outdoor air temperature (OAT) is high enough for
operation
• Compressor operation is not disabled by an alarm
condition
None
Cooling capability is not provided .
Off Ambient
The outdoor air temperature (OAT) is too low for operation .
The OAT becomes too low for operation when it drops below
the OAT cooling lockout setting . OAT becomes high enough for
operation when it rises above the OAT cooling lockout setting
by more than 2°F (adjustable - OAT Diff).
Off Alarm
Compressor operation is disabled by an alarm condition .
Off Network
Control mode is set via the keypad to auto and cooling is
disabled via a network command .
Off Manual
Control mode is set to Fan Only or Heat Only via the keypad
display .
Determining Heat Status
Htg Status is a status item which indicates whether or not the
primary source of heating in the unit is currently allowed . On
heat pump units this is the compressor heating .
The following are descriptions of the heating status states:
Enabled
In the heat pump, compressor heating is enabled if all of the
following are true:
• Control Mode is not set via the keypad to fan only or cool
only
• Control Mode is set via the keypad to auto and heating is
not disabled via a network command
• The outdoor air temperature (OAT) is warm enough
(above 0°F default) and cool enough (below 55°F default)
for compressor heating operation .
None
Unit is not a heat pump and heating capability is not provided
Off Ambient
In a heat pump, the OAT is too high or too low for compressor
heating operation . OAT becomes too high for compressor heat
operation when it rises above the high OAT heating lock out
set point . The OAT becomes low enough for compressor heat
operation when it drops below the high OAT heating lock out
set point by more than the heating lockout differential. The The
OAT becomes too low for compressor heat operation when it
falls below the low OAT heating lock out set point . The OAT
becomes high enough for compressor heat operation when
it rises above the low OAT heating lock out set point by more
than the heating lockout differential.
Off Network
Control Mode is set via the keypad to auto and heating is
disabled via a network command .
Off Manual
Control Mode is set via the keypad to fan only or cool only . .