OM 1263 • MICROTECH UNIT CONTROLLER 38 www .DaikinApplied .com
Trending
Trending
Trending Menus
The Trending Menus allow for setting up and managing onboard
trending of up to 30 data points within the controller . This data
can then be exported to an SD card . The trending memory will
begin over-writing the oldest existing data in the controller’s
memory when the allocated trending memory fills up. If an
SD card is installed in the controllers SD card reader slot, an
automatic export of the data will occur every night at midnight .
Table 30: Trending Menu
Item Display
Name
Default Setting
Range
Password Level
Trending Ena=
No
No/Yes
2
Apply Chgs=
No
No/Yes
2
Sample Time=
300s
1-3600s
2
TrendOnOff=
Off
Off/On
2
AutoExpTime=
1440m
0-1440m
2
Export Data=
No
No/Yes
2
Clear Trend=
Done
Done
2
ClrData
2
ClrCfg
2
TrendFull=
Wrap
Wrap/Stop
2
DefaultTrend=
No
No/Yes
2
Trending Ena
is an adjustable item which enables and
disables the on board trending function .
Apply Changes
is an adjustable item which must be set to
make changes to trending point definitions and sampling rate
take effect.
Sample Time
is an adjustable item used to the sampling rate
for trending data points .
TrendOnOff
is an adjustable item which starts and stops the
on board trending function .
AutoExpTime
is the length of time a trend is to be captured
Export Data
is an adjustable item which initiates a manual
export of the current on board trend data to an SD card .
Clear Trend
is an adjustable item used to either clear only the
current trend data or the entire trend configuration.
TrendFull
is a writable input that allows the user to define
once the trend is recorded to either stop recording or begin to
overwright the beginning of the trend
DefaultTrend
is a status to reset all trend reading back to the
unit default settings or not .
Default
There are thirty default trend points for ROC . They will only not
be recorded if manually programmed not to record .
Table 31: Default Trends Menu
Item Display
Name
Default Setting
Range
Password Level
Point 1=
INV%
INV%
2
Point 2=
STDOut
STDOut
2
Point 3=
SAF%
SAF%
2
Point 4=
EF%
EF%
2
Point 5=
OAD%
OAD%
2
Point 6=
RH%
RH%
2
Point 7=
H/COut
H/COut
2
Point 8=
OAT
OAT
2
Point 9=
ClgSt
ClgSt
2
Point 10=
HtgSt
HtgSt
2
Point 11=
Cap%In
Cap%In
2
Point 12=
INVCmd
INVCmd
2
Point 13=
CmpInLk
CmpInLk
2
Point 14=
PTD
PTD
2
Point 15=
PTS
PTS
2
Point 16=
EVI%
EVI%
2
Point 17=
EVO%
EVO%
2
Point 18=
OAFCmd
OAFCmd
2
Point 19=
OF1Spd
OF1Spd
2
Point 20=
OF2Spd
OF2Spd
2
Point 21=
Tc
Tc
2
Point 22=
TcSpt
TcSpt
2
Point 23=
DSH
DSH
2
Point 24=
Teg
Teg
2
Point 25=
SSH
SSH
2
Point 26=
SSHSpt
SSHSpt
2
Point 27=
HDRT1
HDRT1
2
Point 28=
HDRT3
HDRT3
2
Point 29=
OilSts
OilSts
2
Point 30=
OilMng
OilMng
2