PHA = Phase failure
UzLow = DC-Link Undervoltage
UzHigh = DC-Link Overvoltage
UeHigh = Mains Overvoltage
UeLow = Mains Undervoltage
Question:
• Can the main voltage be measured at any spot; a data logger may be helpful .
No:
Measure the voltage at the power supply input of the concerned fan .
Corrective:
• Reset the failure; re-start the motor and observe it .
• If applicable, filter out the source of disturbing signal.
Repeated occurrence:
Question:
• Do other fans show the same failure?
• How often does the failure occur?
• Get big electrical consumer loads switched at the same time when the failure occurs in the surrounding area?
• Are compressors or large asynchronous motors applied within the arrangement?
Yes:
Systematic search for external disturbance voltage peaks; If applicable, usage of data logger for a longer
period and analysis of the measured values .
• Are the voltage values within the specified range?
No:
It seems to be a hardware problem of the fan . Fan need to be replaced .