ED 15062-7 • MICROTECH II CHILLER CONTROLLER 64
www.DaikinApplied.com
d
eTaIled
d
aTa
P
oInT
I
nformaTIon
Evaporator Leaving Water Temperature for Compressor
Keypad Menu Path:
Menu
\View
\Comp
Measurement
Units
Data Type
Valid Range
Default Value
Temperature
BACnet: °F
BACnet: Real
BACnet: -40°–244°F
NA
BACnet
Compressor Select
This output network variable indicates the current temperature of the Evaporator leaving chilled water temperature of the
compressor selected with
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
23
Present Value
85
Object Name
LvgEvapWaterTempComp
Compressor #2
This variable indicates the current temperature of the Evaporator leaving chilled water temperature of compressor 2. Not available
on all chiller models. (A87)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
68
Present Value
85
Object Name
Comp2EvapLvgWTmp