ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Compressor Status
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates the number status of the compressor.
Measurement
Units
Data Type
Valid Range
Default Value
Event Count
NA
BACnet: Real
LONWORKS: Fixed Point
Scalar - unsigned long
0–31
NA
BACnet
Compressor Select
This output network variable indicates the compressor status of the compressor selected with
. (I44)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
123
Present Value
85
Object Name
CompressorStatus
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown
Compressor #2
This output network variable indicates the compressor status of the compressor 2. (I105)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
91
Present Value
85
Object Name
Comp2Status
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown
Compressor #3
This output network variable indicates the compressor status of the compressor 3. (I108)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
99
Present Value
85
Object Name
Comp3Status
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown